50
Expert-50 rev.10
Expert-50
The following diagram explains how temperature alarms are detected:
When the average room temperature exceeds the high temperature alarm
setting, a high temperature alarm is generated. When the average room
temperature drops below the low temperature alarm setting, a low tem-
perature alarm is generated. Note that an alarm condition must remain
active at least 30 seconds to be considered as an alarm.
Room
Tempera-
ture
Set Point
High T°
Time
High Temperature Alarm
Low T°