53
Expert-50 rev.10
TEST MODE
A test mode allows you to simulate temperature changes and verify con-
troller performance. In test mode, the room temperature probe inputs are
turned off, allowing the user to change the temperature used by the con-
troller to operate the stages. The controller operates as before using the
new temperature settings. The user can also activate each output sepa-
rately.
Adjusting Room Temperature
When the room temperature is adjusted, the controller bypasses the tem-
perature probe inputs and uses the new value as a reference.
Set the function to
TEST
using the
menu select buttons. The room tem-
perature bypass value is displayed.
Press the Edit key. The bypass value flashes. Use the arrow keys to
set the bypass value to the desired value. The appropriate outputs are
activated or deactivated immediately following the new temperature
setting.
Activating Individual Outputs
Set the function to
TEST
using the menu select buttons. The room
temperature bypass value is displayed.
Press the down-arrow key. The dis-
play shows "no output" meaning no
output is activated. Press the Edit
key. The Heater 8 output is acti-
vated and "heater 8" flashes on the display. Use the
output select
buttons
to activate individual outputs in turn. To return to normal
operations, press the Edit key or select another function.
Room T° bypass:
76.7°F
Select. output:
no output