41
Expert-50 rev.10
Expert-50
Adjusting Fan Start Temperatures
Note that the minimum temperature difference between two consecu-
tive start temperatures is 0.5°F and the maximum is the value defined in
the user setup. Note also that start temperatures for all consecutive
stages are adjusted by the same amount. The stop temperature is
automatically adjusted according to the common differential setting.
Set the function to
SETTINGS –
OUTPUTS
using the menu select
buttons. The start and stop tem-
peratures for Heater 8 are displayed
and the Heater 8 LED on the right
flashes.
Use the output select buttons to select the fan stage to adjust. The
corresponding LED on the right of the front panel flashes.
Press Edit key. The start temperature flashes. Use the arrow keys
to adjust the start temperature to the desired value.
Start: 76.5°F
Stop: 75.5°F