The Expert-50 has eight independent heater stages. A start and stop
temperature is defined by the user for each stage. The stop temperature
must be at least 0.5°F greater than the start temperature for a given
heater. Start temperatures can be up to 14.5°F greater than the set
point. A start temperature above the set point is used for controlling
heat mats, for example. The number of heater stages needed and the
probe assignments for each stage are determined during the controller
setup. The following diagram shows the operation of the heaters.
HEATER SETTINGS
Heater turns off
Temperature
Heating
ON
OFF
Heater turns on
Set Point
STOP
TEMP.
START
TEMP.