Use the output select buttons to select
ALARM
. The corresponding
LED on the right of the front panel flashes. The high and low alarm
temperatures are displayed.
Press down-arrow key three
times. The high and low alarm
pressures are displayed.
Press Edit key. The low alarm pressure value flashes. Use the arrow
keys to adjust the low alarm pressure to the desired value.
Press Edit key. The high alarm pressure value flashes. Use the arrow
keys to adjust the high alarm pressure to the desired value.
5
Adjusting Water Spill Alarm
The controller sounds an alarm if the water consumption exceeds the
water spill limit in a 15-minute delay. The water consumption alarm limit
can be adjusted from 0 to 65000 gallons (or liters) per 15 minutes.
Set the function to
START/STOP TEMPERATURE
using the menu
select buttons. The start and stop temperatures for Heater 8 are
displayed and the Heater 8 LED on the right flashes.
Use the output select buttons to select
ALARM
. The corresponding
LED on the right of the front panel flashes. The high and low alarm
temperatures are displayed.
Press down-arrow key four times.
The maximum water consumption
is displayed.
Press Edit key. The maximum water consumption flashes. Use the
arrow keys to adjust the water consumption to the desired value.
Water Spill
Limit: 10Gal
Low: .00"WC
High: .10"WC