55
Expert-32P rev.11
Expert-32P
7
Adjusting Static Pressure Alarm Delay
An alarm is set off if the static pressure level exceeds the acceptable
pressure range. The alarm condition must be maintained during a certain
delay before the alarm sets off. This delay can be adjusted from 0 to 900
seconds.
Set the function to
VENT DOORS
using the menu select buttons.
Winter's high and low pressure set points are displayed.
Press the down-arrow key to select
the "static pressure alarm delay"
menu.
Press the Edit key. The alarm delay flashes on the display. Use the
arrow keys to adjust the delay to the desired value.
Pressure alarm
Delay: 300sec