13
Expert-32P rev.11
Expert-32P
2. Time of Day Format:
Press the Edit
key to select either AM-PM or 24H time.
3. Number of Temperature Probes in the
Room
: Press the Edit key to set the num-
ber of room temperature probes wired in
the controller (whether they are selected
or not). Note that probes must be wired from left to right following the
numerical order of the terminals on the board if 6 probes are not needed.
4. Probe Set 2 Starting Stage
: This
parameter determines the fan stage at
which probe set 2 is used to calculate
the average temperature. Press the Edit
key to set the fan stage number (set to OFF to use only one probe set).
5. Probe Set 1 - Probes Used
: The se-
lected probes for probe set 1 flash on
the display. Press the Edit key and use
the arrow keys to select or deselect each
probe individually for set 1.
6. Probe Set 2 - Probes Used
: The
selected probes for probe set 2 flash on
the display. Press the Edit key and use
the arrow keys to select or deselect each
probe individually for set 2.
7. Use Humidity Sensor
: Press the Edit
key and set to YES if a relative humidity
sensor is connected to the unit.
8. Use Water Meter
: Press the Edit key
and set to YES if a water meter is con-
nected to the unit.
9. Use Outside Temperature Probe
:
Press the Edit key and set to YES if an
outside temperature sensor is used.
Time of day
format: AM-PM
#T° sensors
in the room: 6
Use probes set2
at stage: OFF
Set 1 Probes
123456
Set 2 Probes
123456
Use humidity
sensor(RH)? NO
Use water
meter? YES
Use Out T
sensor? YES