Accessories
41
Cat. No. 01023095
Switch Inputs
Low Pressure Switch
Display says
“OFFLINE”
or “STANDBY”;
then the
SV1 output
is OFF; and
the pump output
is OFF;
display says
“STARTING”,
then the
SV1 output
turns ON;
the pump output
is OFF; and the
“SV1 Delay”
time starts;
at the end of
the “SV1 Delay time;
the unit checks
the pressure
switch input;
If the pressure is ok,
then the
pump starts, and
the display
says ”RUNNING”
Figure 16.
OFFLINE to RUNNING
at the end of
“SV1 Delay time;
the unit checks
the pressure
switch input;
If the pressure
is NOT ok,
then the unit turns
off the SV1 output;
the pump output
stays OFF; and
the displays
says ”OFFLINE”
and “PROBLEM FOUND”
display says
“STARTING”,
then the
SV1 output
turns ON;
the pump output
is OFF; and
the “SV1 Delay”
time starts;
Display says
“OFFLINE”
or “STANDBY”;
then the
SV1 output
is OFF;
and the
pump output
is OFF;
Figure 17.
OFFLINE to PROBLEM FOUND