42
Culligan® Series M2 Reverse Osmosis
42
Cat. No. 01023095
Display says
“RUNNING”,
then
the SV1 output
is ON; and
the pump output
is ON;
the pressure switch
OPENS,
indicating pressure
is NOT ok;
the “PS Sw Delay”
time starts;
the SV1 output
stays ON;
the pump output
stays ON; and
the display still
says “RUNNING”
at the end of the
“PS Sw Delay” time:
If pressure returns
within delay time,
then the unit continues
to run normally;
If the pressure is gone
for the whole delay time,
then the pump output
turns OFF and
the unit goes to
STARTING mode;
this attempt to start is
counted as an “Auto-restart”
at the end of the
“SV1 Delay” time;
the unit checks
pressure switch input;
if pressure is ok,
then the pump
starts and
the display
says “RUNNING”
Figure 18.
Auto-restart
Terms:
“PS Sw Delay”
: This delay applies when the RO is in “RUNNING” mode (pump is actually ON). It determines how long
the pump will continue to run after a loss of pressure at the dry-contact pressure switch input
“SV1 Delay”
: This delay applies when the RO is in “STARTING” mode (pump is actually OFF). It determines how long
the system should stay in “starting mode” before checking the pressure switch status and deciding whether or not to start
the pump.
“Auto-restart”
: In the event of a low pressure shutdown, an auto-restart attempt should be made. Basically, the system
goes into “starting” mode again. There can be a maximum of 5 restart attempts. After the 5th successful restart, the next
low pressure shutdown should put the system into OFFLINE mode with error code “problem found”.
NOTE This five-time counter on the number of restarts allowed resets to zero every night at midnight and
every time that the operator selects YES from the Main Menu/Go to Running screen.
The pressure switch is prewired at the factory to the GBE RO controller AUX board POSITION (J1) pins utilizing pins 2
and 4. The switch is factory set to 18 psi. The pressure can be adjusted from 6 psi to 30 psi by turning the knurled ring on
the body of switch clockwise to increase the pressure and counter-clockwise to decrease. One revolution is approximately
6.5 psi.
Switch Inputs Setup
RUNNING
JAN-01-12 12:01P
1. From the default home screen, press
. The screen displays the main menu.
1) GO TO RUNNING
2) GO TO OFFLINE
3) INFORMATION
>4) SETUP
2. Press
to scroll to 4) SETUP.
3. Press
to select the SETUP menu.