GH DRIVER
9-
12
Function
code
Name
Description
Setting
scope
Unit
Factory
setting
Change
Recommend
motor
D1.39
Carrier wave cycle
0: 8k
1: 4k
2: 16k
0~2
-
0
△
Synchronous/
Asynchronous
D1.40
Save
-
-
-
-
-
-
D1.41
Delta connection
weak field area
current curve
Delta connection weak field area current curve
0~30000
rpm
0
×
Asynchronous
D1.42
Delta connection
constant power
speed
Delta connection constant power maximum
speed
0~6000.0
A
11.0
×
Synchronous/
Asynchronous
D1.43
Speed tolerance
of star and delta
switch
The dead zero of switch star and delta
connection: it is delta connection when
SPD>D1.11+D1.13. It is star when
SPD<D1.11-D1.13. It keep last state when other
situation
0~30000
rpm
0
-
Asynchronous
D1.44
Rated torque
Motor rated torque
0~3000.0
nm
35.0
×
Synchronous/
Asynchronous
D1.45
Switch time of star
and delta
It decided the time of switch enable
0~3000
ms
0
-
Asynchronous
D1.46
Rotor resistance
Rotor resistance setting
0~60.000
Ω
121
×
Asynchronous
D1.47
VFSelection of
Curve Types
0: Custom VF curve
1: Linear curve
2: 2nd power curve
3: Cubic curve
0
~
3
-
1
×
Asynchronous
D1.48
Reactive Current
Correction
Coefficient
Setting of Correction Coefficient of Reactive
Current
0~100.0
-
4
×
Asynchronous
D1.49
Low-pass filter
parameters1
Low Pass Filtering, High Frequency Parameters
0~512
-
276
×
Asynchronous
D1.50
Low-pass filter
parameters2
Low-pass filtering, low-frequency parameters
0~512
-
25
×
Asynchronous
D1.51
Minimum Output
Frequency
Minimum Output Frequency Setting of Motor
0~50
Hz
0.5
×
Asynchronous
D1.52
Minimum Output
Frequency Voltage
Setting of the lowest output frequency and
voltage of motor
0~400
V
5
×
Asynchronous
D1.53
Intermediate output
frequency
Intermediate Output Frequency Setting of Motor
0~50
HZ
25
×
Asynchronous
D1.54
Intermediate
Output Frequency
Voltage
Setting of intermediate output frequency and
voltage of motor
0~400
V
200
×
Asynchronous
D1.55
Rated Output
Frequency
Rated Output Frequency Setting of Motor
0~50
HZ
50
×
Asynchronous