GH DRIVER
9-
16
Function
code
Name
Description
Setting
scope
Unit
Factory
setting
Change
Recommend
motor
T1.28
Mechatrolink II
Selection of Bus
Master Station
0: New Algebraic Control System
1: Baoyuan CNC System
2: Baoyuan turret
3: Baoyuan ATC
4: KND CNC System
0~4
-
1
×
Synchronous/
Asynchronous
T1.29
Bus execution time Bus execution interval period
1~65535
ms
0
*
Synchronous/
Asynchronous
T1.30
Save
-
-
-
-
-
-
~
T1.35
T1.36
Monitoring
Selection of Broad
Number System1
Return the torque and current to the system
when the speed of the system's return motor is
set to 12 hours
10h
、
12h
-
10h
○
Synchronous/
Asynchronous
T1.37
Monitoring
Selection of GST
System2
Return the torque and current to the system
when the speed of the system's return motor is
set to 12 hours
10h
、
12h
-
12h
○
Synchronous/
Asynchronous
T1.38
save
-
-
-
-
-
-
~
T1.47
T1.48
Mechatrolink speed
deceleration ratio
molecule
Setting Mechatrolink speed deceleration ratio
molecule
0~65535
-
0
○
Synchronous/
Asynchronous
T1.49
Mechatrolink speed
deceleration ratio
denominator
Setting Mechatrolink speed deceleration ratio
denominator
0~65535
-
0
○
Synchronous/
Asynchronous
T1.50
CAN station No set
0: Master station
1: Slave station
0~9
-
0
△
Synchronous/
Asynchronous
T1.51
CAN terminal
resistance select
CAN terminal resistance select
0
,
1
-
0
○
Synchronous/
Asynchronous
T1.52
CAN slave station
number select
Slave station number select
0~255
-
0
○
Synchronous/
Asynchronous
T1.53
CAN communication
task cycle set
When the value is 0, adjust cycle shall be worked
as per default 2ms and set resolution as 0.1ms
0.5~50.5
0.1ms
1.0
×
Synchronous/
Asynchronous
T1.54
CAN protocol
selection
0: CTB protocol
1: 402 protocol
0
,
1
-
0
○
Synchronous/
Asynchronous
T1.55
CANOPEN time-out
CANOPEN time-out time setting, start the
function when it isn’t 0
0~30000
ms
0
○
Synchronous/
Asynchronous
T1.56
CANOPEN baud
rate
Setting CAN baud rate by the parameter, if it
want to set 500k, the parameter write 500
0~65535
KBPS
500
△
Synchronous/
Asynchronous
T1.57
CANOPENBit
control
bit0: Limiting function
0: Disability
1: Enable
0~65535
-
0
○
Synchronous/
Asynchronous