6
I. Pre-Installation
WARNING
Carefully read all instructions before installing
boiler. Failure to follow all instructions in proper
order can cause personal injury or death.
A
.
Inspect shipment
carefully for any signs of damage.
All equipment is carefully manufactured, inspected
and packed. Our responsibility ceases upon delivery
of boiler to carrier in good condition. Any claim
for damage or shortage in shipment must be filed
immediately against carrier by consignee. No claims
for variances or shortages will be allowed by Boiler
Manufacturer, unless presented within sixty (60) days
after receipt of equipment.
B.
Installation must conform
to the requirements of
the authority having jurisdiction. In the absence of
such requirements, installation must conform to the
National Fuel Gas Code
, NFPA 54/ANSI Z223.1.
Where required by the authority having jurisdiction, the
installation must conform to the
Standard for Controls
and Safety Devices for Automatically Fired Boilers
,
ANSI/ASME No CSD-1.
C.
Provide clearance between combustible material
and
boiler jacket (following clearances are minimums):
1. 16H-340: listed for Alcove installation
a. Front: 18”
b. Top: 36”
c. Draft hood, rear, sides and flue connector: 6”
WARNING
Appliance is design certified for installation on
noncombustible flooring only. For installation
on combustible flooring only when installed on
special base listed in Table 2. Boiler must not be
installed on carpeting. When boiler is installed on
concrete which is over a material that is subject
to melting (PVC, PEX radiant tubing, etc.), the
special base must be used. A concrete pad is not
sufficient to protect combustible flooring.
2. 16H-410-16H-505: for installation in room which is
large in comparison with size of boiler.
a. Front: 18”
b. Top: 51½”
c. Draft hood, rear, sides, and flue connector: 6”
D.
Provide clearance for servicing
and proper operation
(following clearances are recommended and may be
reduced to minimum clearances shown above):
1. Single boiler, 16H-340, Front: 24” (61.0 cm)
2. Single boiler, 16H-410-16H-505, Front: 48”
(122.0 cm)
3. Multiple/modular boiler, Sides: 1” (2.5 cm)
E.
Install boiler on level floor
as close to chimney as
possible. For basement installation provide a solid base
such as concrete or masonry construction if floor is not
level or if water may be encountered on floor around
boiler.
F.
Protect gas ignition system components
from
water (dripping, spraying, rain, etc.) during boiler
operation and service (circulator replacement, control
replacement, etc.).
G.
Provide combustion and ventilation air
in accordance
with applicable provisions of local building codes, or
the
National Fuel Gas Code
, NFPA 54/ANSI Z223.1,
Air for Combustion and Ventilation.
WARNING
Adequate combustion and ventilation air must be
provided to assure proper combustion.
The following guideline is based on the
National Fuel
Gas Code
, NFPA 54/ANSI Z223.1.
1. Determine volume of space (boiler room). Rooms
communicating directly with space (through
permanent openings not furnished with doors) are
considered part of space.
Volume [ft
3
] = Length [ft] x Width [ft] x Height [ft]
2. Determine Total Input of all appliances in space.
Round result to nearest 1,000 Btu per hour (Btuh).
3. Determine type of space. Divide Volume by Total
Input.
a. If result is greater than or equal to 50 ft
3
per
1,000 Btuh, space is considered an
unconfined
space
.
b. If result is less than 50 ft
3
per 1,000 Btuh, space
is considered a
confined space
.
4. Determine building type. A building of
unusually
tight construction
has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a
Boiler Model
Special Base Part Number
16H-340
61816075
16H-410
61816085
16H-460
61816095
16H-505
61816105
Table 2: Special Base Required for Installation on
Combustible Flooring
Содержание 16H-340
Страница 11: ...11 Figure 6 Flame Roll out Switch Installation Figure 7 Burner Burner Access Panel Installation ...
Страница 13: ...13 Figure 8 Jacket Assembly ...
Страница 14: ...14 Figure 9 EP CSD 1 Control Installation ...
Страница 16: ...16 Figure 11 Main Gas Piping Intermittent Ignition EI ...
Страница 17: ...17 Figure 12 Schematic Pilot Piping Honeywell EI USA ...
Страница 18: ...18 Figure 15 Schematic Gas Piping EP CSD 1 Control System 16H 410 16H 505 ...
Страница 31: ...31 Figure 31 Wiring Diagram Honeywell EI USA Intermittent Circulation 16H 340 16H 510 MegaStor Relay MegaStor ...
Страница 37: ...37 Figure 41 Operating Instructions EI ...
Страница 47: ...47 Honeywell EI Trouble Shooting Guide ...
Страница 48: ...48 THIS PAGE LEFT BLANK INTENTIONALLY ...
Страница 58: ...58 ...
Страница 60: ...60 ...