background image

 

-

 Page  13 -

 

Functions - LEVELLER menu 

SW1 

Save? 

L07 

Set limit for service interval in operating time (in 24h days) 
(default 365 days). Service interval disabled when set to 0. 

+1 Yes 

L08 

Address of the control unit on CMS-network (1-255) (default 255). 

+1 

Yes 

L09 

CMS-Network baudrate (U00=38400bps (default) or 
 U01=187500 bps).

 

+1 Yes 

L10 

Auto return with one or two press on AUTO button. 
U00=Leveller, door and shelter returns. (default) 
U01=Leveller return on first press, door and shelter on next press.

 

+1 Yes 

L11 

External interlock of leveller (S9). 
U00= door photocell to detect open door. 
U01= door limit switch to detect open door. (default) 
U02= CDM9 to detect open door (from a pre-selected door pos.). 
Run the door to the wanted position go in and set L11 to UO2. 

+1 Yes 

L12 

Hydraulic motor current adjustment. 
2.6A 
3.2A  
3.8A 
4.4A (default SwingDock). 
5.0A  
5.6A (default TeleDock). 
6.2A 
6.8A 
7.4A 
8.0A 
8.6A 
9.2A 

+1 Yes 

L13 

Cross-traffic switch (S6) exist or not. 
U00= Cross-traffic switch installed. 
U01= No switch installed (door located behind leveller). (default).

 

+1 Yes 

L14 

Lift/swing lip extend

 

timer T2 1 – 19sec. (default 5sec.).

 

+1 Yes 

L15 

Swing lip fold in timer T3 5 – 20sec. (default 11sec.). 

+1 

Yes 

L16 

Return leveller timer T4 3 – 30sec. (default swingdock 5sec. 
teledock 9sec.).

 

+1 Yes 

L17 

RZ-Automatic timer T5 0 – 2.0sec. (default 0sec.). 

+0,1 

Yes 

L18 

Start shelter - open door timer T6 0 – 30sec. (default 10sec.). 

+1 

Yes 

L19 

Close door – stop shelter timer T7 0 – 30sec. (default 30sec.). 

+1 

Yes 

L20 

Service reset (total) 
Change to U01 and save.  
(Resets all error lists and counters for leveller and door). 

+1 

 

Yes 

 

L21 

Lock/unlock Control unit (default U00). 
U00 = Unlock control unit. 
U01 = Lock control unit (a key is shown in the display). 

+1 Yes 

L22 

Numbers of valves for Swingdock. (default U00). 
U00 = Default by variant detection in button panel on the lid. 
U01 = Swingdock one valve function (overrides variant detection). 
U02 = Swingdock two valves function (overrides variant detection).

+1 Yes 

 
 
 
 
 
 

 
 
 
 
 
 

 
 
 
 
 
 

 
 
 
 
 
 

Содержание ECS 950

Страница 1: ...Service tool manual ECS 950 950 Docking Approv Godk Doc No Rev O K046804 2010 12 01 KHm GB...

Страница 2: ...display 10 1 10 Automatic closing activated 10 2 1 Normal Service Technician work procedure 15 2 2 How do I do to 17 2 2 1 See a non changeable register 17 2 2 2 Set the limits for service interval 17...

Страница 3: ...rors from the leveller and fifteenth latest errors from the door As default the state of the leveller shelter or the door will be displayed on the control box and on the display of the service tool In...

Страница 4: ...choices The LEFT BUTTON SW1 will in some menus increase the value by 1 In other menus the value shown is set to 0 if you press the LEFT BUTTON SW1 An overview of these choices can be seen in the colu...

Страница 5: ...val Since the Service interval in number of door cycles is set in menu d07 one needs to reset d04 at service Since the Service interval in operating time is set in menu d08 one needs to reset d06 at s...

Страница 6: ...p of CDM9 operator Refresh No d0C Shows the active door errors with highest priority first 1 No d0d Set functionality of Auto close timer No C card 0 Close the door and retracts the shelter 1 Close th...

Страница 7: ...o 1 6 3 and 1 6 4 Remember that it is only possible to reset the trip meter and not the total counter or Odometer 8 Now one may change the service interval if there is a need for another interval than...

Страница 8: ...eveller shelter or the door B Press LEFT BUTTON SW1 3 times menu d is showed Select Door submenu by RIGHT BUTTON SW2 d01 is showed C Press SW1 several times until submenu d07 or d08 see Table 1 is sho...

Страница 9: ...d01 is showed C Press SW1 several times until submenu d04 is showed Select the submenu by RIGHT BUTTON SW2 The display now shows the number of cycles that is stored for example 99 D Press the LEFT BU...

Страница 10: ...01 is showed C Press SW1 several times until submenu d0C is showed Select the submenu by RIGHT BUTTON SW2 The display now shows the error with the highest priority D Press the LEFT BUTTON SW1 to see n...

Страница 11: ...the control box in immediate proximity to the connection blocks In order to prevent the components from being destroyed by static electricity during installation or service work any staff coming into...

Страница 12: ...rmation about errors that recently appeared on the leveller While troubleshooting the leveller you can find important information in this menu If you need to contact CPAB helpdesk regarding the contro...

Страница 13: ...6 2A 6 8A 7 4A 8 0A 8 6A 9 2A 1 Yes L13 Cross traffic switch S6 exist or not U00 Cross traffic switch installed U01 No switch installed door located behind leveller default 1 Yes L14 Lift swing lip e...

Страница 14: ...shelter open door U01 Close door stop shelter U02 Open door outside U03 Autoclose of door on off U04 doors extra safety default U05 Close door U06 Open door open in the lid disconnected 1 Yes L26 The...

Страница 15: ...1 and save The functions are now as pre set from factory 1 Yes Table 2 Functions SHELTER menu SW1 Save S01 Show the total number of shelter cycles x1 Refresh No S02 Shelter type default SIR U00 SIR U0...

Страница 16: ...the trip meter and not the total counter or Odometer It is also possibly to do a total service reset via submenu L20 which is explained in detail in 2 2 5 8 Now one may change the service interval if...

Страница 17: ...L is showed Enter Leveller submenu by RIGHT BUTTON SW2 L01 is showed C Press SW1 several times until submenu L06 or L07 see Table 1 is showed Enter for example the submenu L06 by RIGHT BUTTON SW2 the...

Страница 18: ...it from service menu Alternatively press LEFT BUTTON SW1 continuously for 2sec to exit from service menu G The display now goes back to normal operation showing the state of the leveller shelter or th...

Страница 19: ...error in the RAM memory area on the Leveller board has been detected The error is considered as a fatal error and the entire system will be halted until the power supply has been switched off F10 Fau...

Страница 20: ...t from service menu N The display now goes back to normal operation showing the state of the leveller shelter or the door Alternatively the display showing active error codes 2 4 Indication of time fo...

Страница 21: ...ress LEFT BUTTON SW1 continuously for 2sec to exit from service menu F The display now goes back to normal operation showing the state of the leveller shelter or the door 3 1 2 Set Shelter type A The...

Страница 22: ...ton S8 OPEN DOOR S00 will be displayed for 2 sec and winter mode is selected Function to summer mode Shelter function disabled The Leveller in resting position door closed and the shelter switched off...

Страница 23: ...the control box in immediate proximity to the connection blocks In order to prevent the components from being destroyed by static electricity during installation or service work any staff coming into...

Отзывы: