 Page  6 -

 

 
 

Functions – DOOR menu 

SW1 

Save? 

d01 

Show time for automatic closing T1 (If C-card in seconds, if 
Leveller card in minutes). 

Refresh No 

d02 

Set time for pre-flashing T2 1 – 32 sec (default 10 sec). 

+1 

Yes 

d03 

Show the total number of door cycles (x1). (If C-card: x1000) 

Refresh 

No 

d04 

Show the total number of door cycles (x1). (If C-card: x1000) 
Resettable by SW1. 

0 Yes 

d05 

Show the total operating time (in 24h days). 

Refresh 

No 

d06 

Show the total operating time (in 24h days). Resettable by SW1. 

Yes 

d07 

Set a limit for service interval in number of door cycles (x1000) 
(default 20 000 cycles). Service interval disabled when set to 0. 

+1 Yes 

d08 

Set limit for service interval in operating days (default 365 days). 
Service interval disabled when set to 0. 

+1 Yes 

d09 

Show the door error log with the most recent error first. 

+1

1

 Yes 

d0A 

Set automatic exit from service menu after 30 seconds if SW1 or 
SW2 has not been pressed. 

0

 = Automatically exit the menu system after time-out (default          

when power on). 

1

 = Automatically exit the menu system disabled. 

0/1

2

 Yes 

d0b 

Show current torque step of CDM9 operator.

 

Refresh No 

d0C 

Shows the active door errors with highest priority first. 

+1 

No 

d0d 

Set functionality of Auto close timer. (No C-card) 
0 = Close the door and retracts the shelter. 
1 = Close the door (default). 

+1 Yes 

d0E 

Set Door mode. (No C-card) 
0 = Hold-to-run-down mode. 

Sets automatically L10 = U01.

 

1 = Normal mode (default). 

NOTE!

 Only to avoid E04 in 920-mode. 

2 = External control unit, ECS 400 
Full function on external inputs-outputs will not be possible!

 

+1 Yes 

Table 1 

950 - 

Start Here! 

1:5      Normal Service Technician work procedure 

1.

 

For 950 control box: Service lamp is ON.  

2.

 

Remove the screws and open the control box. 

3.

 

Attach the Service Tool cable on the connector X2 on leveller board or J2 on processor 
C-board in the control box. 

4.

 

The display shall now show the same information as the display on the outside of the 
control box. 

5.

 

Follow the instructions in §1.6.1 and choose submenu d03 in menu [d] which is the total 
number of door cycles counter. Look in the service manual to see which service the 

                                                 

1

 Next error in order of priority (most recent error first), when the error log has come to the end then ”END” is 

shown.  

2

 Automatic exit from menu system = 0, otherwise =1. SW1 is alternating between 0 and 1. This function is not 

saved in memory after a power break.  

Содержание ECS 950

Страница 1: ...Service tool manual ECS 950 950 Docking Approv Godk Doc No Rev O K046804 2010 12 01 KHm GB...

Страница 2: ...display 10 1 10 Automatic closing activated 10 2 1 Normal Service Technician work procedure 15 2 2 How do I do to 17 2 2 1 See a non changeable register 17 2 2 2 Set the limits for service interval 17...

Страница 3: ...rors from the leveller and fifteenth latest errors from the door As default the state of the leveller shelter or the door will be displayed on the control box and on the display of the service tool In...

Страница 4: ...choices The LEFT BUTTON SW1 will in some menus increase the value by 1 In other menus the value shown is set to 0 if you press the LEFT BUTTON SW1 An overview of these choices can be seen in the colu...

Страница 5: ...val Since the Service interval in number of door cycles is set in menu d07 one needs to reset d04 at service Since the Service interval in operating time is set in menu d08 one needs to reset d06 at s...

Страница 6: ...p of CDM9 operator Refresh No d0C Shows the active door errors with highest priority first 1 No d0d Set functionality of Auto close timer No C card 0 Close the door and retracts the shelter 1 Close th...

Страница 7: ...o 1 6 3 and 1 6 4 Remember that it is only possible to reset the trip meter and not the total counter or Odometer 8 Now one may change the service interval if there is a need for another interval than...

Страница 8: ...eveller shelter or the door B Press LEFT BUTTON SW1 3 times menu d is showed Select Door submenu by RIGHT BUTTON SW2 d01 is showed C Press SW1 several times until submenu d07 or d08 see Table 1 is sho...

Страница 9: ...d01 is showed C Press SW1 several times until submenu d04 is showed Select the submenu by RIGHT BUTTON SW2 The display now shows the number of cycles that is stored for example 99 D Press the LEFT BU...

Страница 10: ...01 is showed C Press SW1 several times until submenu d0C is showed Select the submenu by RIGHT BUTTON SW2 The display now shows the error with the highest priority D Press the LEFT BUTTON SW1 to see n...

Страница 11: ...the control box in immediate proximity to the connection blocks In order to prevent the components from being destroyed by static electricity during installation or service work any staff coming into...

Страница 12: ...rmation about errors that recently appeared on the leveller While troubleshooting the leveller you can find important information in this menu If you need to contact CPAB helpdesk regarding the contro...

Страница 13: ...6 2A 6 8A 7 4A 8 0A 8 6A 9 2A 1 Yes L13 Cross traffic switch S6 exist or not U00 Cross traffic switch installed U01 No switch installed door located behind leveller default 1 Yes L14 Lift swing lip e...

Страница 14: ...shelter open door U01 Close door stop shelter U02 Open door outside U03 Autoclose of door on off U04 doors extra safety default U05 Close door U06 Open door open in the lid disconnected 1 Yes L26 The...

Страница 15: ...1 and save The functions are now as pre set from factory 1 Yes Table 2 Functions SHELTER menu SW1 Save S01 Show the total number of shelter cycles x1 Refresh No S02 Shelter type default SIR U00 SIR U0...

Страница 16: ...the trip meter and not the total counter or Odometer It is also possibly to do a total service reset via submenu L20 which is explained in detail in 2 2 5 8 Now one may change the service interval if...

Страница 17: ...L is showed Enter Leveller submenu by RIGHT BUTTON SW2 L01 is showed C Press SW1 several times until submenu L06 or L07 see Table 1 is showed Enter for example the submenu L06 by RIGHT BUTTON SW2 the...

Страница 18: ...it from service menu Alternatively press LEFT BUTTON SW1 continuously for 2sec to exit from service menu G The display now goes back to normal operation showing the state of the leveller shelter or th...

Страница 19: ...error in the RAM memory area on the Leveller board has been detected The error is considered as a fatal error and the entire system will be halted until the power supply has been switched off F10 Fau...

Страница 20: ...t from service menu N The display now goes back to normal operation showing the state of the leveller shelter or the door Alternatively the display showing active error codes 2 4 Indication of time fo...

Страница 21: ...ress LEFT BUTTON SW1 continuously for 2sec to exit from service menu F The display now goes back to normal operation showing the state of the leveller shelter or the door 3 1 2 Set Shelter type A The...

Страница 22: ...ton S8 OPEN DOOR S00 will be displayed for 2 sec and winter mode is selected Function to summer mode Shelter function disabled The Leveller in resting position door closed and the shelter switched off...

Страница 23: ...the control box in immediate proximity to the connection blocks In order to prevent the components from being destroyed by static electricity during installation or service work any staff coming into...