Functions – DOOR menu
SW1
Save?
d01
Show time for automatic closing T1 (If C-card in seconds, if
Leveller card in minutes).
Refresh No
d02
Set time for pre-flashing T2 1 – 32 sec (default 10 sec).
+1
Yes
d03
Show the total number of door cycles (x1). (If C-card: x1000)
Refresh
No
d04
Show the total number of door cycles (x1). (If C-card: x1000)
Resettable by SW1.
0 Yes
d05
Show the total operating time (in 24h days).
Refresh
No
d06
Show the total operating time (in 24h days). Resettable by SW1.
0
Yes
d07
Set a limit for service interval in number of door cycles (x1000)
(default 20 000 cycles). Service interval disabled when set to 0.
+1 Yes
d08
Set limit for service interval in operating days (default 365 days).
Service interval disabled when set to 0.
+1 Yes
d09
Show the door error log with the most recent error first.
+1
Yes
d0A
Set automatic exit from service menu after 30 seconds if SW1 or
SW2 has not been pressed.
0
= Automatically exit the menu system after time-out (default
when power on).
1
= Automatically exit the menu system disabled.
0/1
Yes
d0b
Show current torque step of CDM9 operator.
Refresh No
d0C
Shows the active door errors with highest priority first.
+1
No
d0d
Set functionality of Auto close timer. (No C-card)
0 = Close the door and retracts the shelter.
1 = Close the door (default).
+1 Yes
d0E
Set Door mode. (No C-card)
0 = Hold-to-run-down mode.
Sets automatically L10 = U01.
1 = Normal mode (default).
NOTE!
Only to avoid E04 in 920-mode.
2 = External control unit, ECS 400
Full function on external inputs-outputs will not be possible!
+1 Yes
Table 1
950 -
Start Here!
1:5 Normal Service Technician work procedure
1.
For 950 control box: Service lamp is ON.
2.
Remove the screws and open the control box.
3.
Attach the Service Tool cable on the connector X2 on leveller board or J2 on processor
C-board in the control box.
4.
The display shall now show the same information as the display on the outside of the
control box.
5.
Follow the instructions in §1.6.1 and choose submenu d03 in menu [d] which is the total
number of door cycles counter. Look in the service manual to see which service the
1
Next error in order of priority (most recent error first), when the error log has come to the end then ”END” is
shown.
2
Automatic exit from menu system = 0, otherwise =1. SW1 is alternating between 0 and 1. This function is not
saved in memory after a power break.