 Page  5 -

 

1:4  

DOOR

 - Menu choices in the display is [d] 

 
A brief description of the menu choices available by SW1 and SW2 are shown in Table 1 for 
Doors, below. 
The table shows information about the function of the SW1 button (which is different in the 
different menus) and if it is possible to store values in the internal memory within the menu. 
 
In menus d04 and d06 it is also possible to reset the counters. This is done by pressing the 
LEFT BUTTON (SW1), and then by storing the new value as 0 back to the internal memory by 
first pressing SW2 and then simultaneously pressing SW1 (meaning both buttons are pressed 
at the same time). 
 
In menus d07 and d08,

 

the service

 interval 

is set. It is the number of door cycles (x1000) or 

operating time (in days) that trigs the 

service-warning lamp 

indicating 

time for service. 

SW1 increases the value by 1 unit. By setting a service interval to 0, the function is disabled 
and the 

service-warning lamp 

will not indicate 

time for service

 for this service interval. 

 

Since the Service interval, in number of door cycles, is set in menu d07, one needs to 
reset d04 at service. 
 
Since the Service interval, in operating time, is set in menu d08, one needs to reset d06 
at service.

 

 
With the help of menu d09, it is possible to see the 

error log

 

door

 that is present in the 

system. 
The error log contains important information about errors that recently appeared on the door. 
 
While troubleshooting the door you can find important information in this menu. If you need to 
contact CPAB-helpdesk regarding the operator and/or software it is important to write down 
the information in the error log. 
When you enter menu d09 you see the error code for the most recently occurred error in the 
system. With SW1 you could step backwards in the error log. When you have reached the 
oldest error code (number 15) you see the message 

“End”

, after pressing SW1. 

 
 

How to erase the error log 

Step to menu d09 with SW1. Enter with SW2. Now press SW2 and then SW1, keep them 
pressed simultaneously for a couple of seconds. When the buttons is released, you will see 
the message “End”. The error log is now erased and the change is saved. 
 
These settings will not disappear after a power reset.  

Содержание ECS 950

Страница 1: ...Service tool manual ECS 950 950 Docking Approv Godk Doc No Rev O K046804 2010 12 01 KHm GB...

Страница 2: ...display 10 1 10 Automatic closing activated 10 2 1 Normal Service Technician work procedure 15 2 2 How do I do to 17 2 2 1 See a non changeable register 17 2 2 2 Set the limits for service interval 17...

Страница 3: ...rors from the leveller and fifteenth latest errors from the door As default the state of the leveller shelter or the door will be displayed on the control box and on the display of the service tool In...

Страница 4: ...choices The LEFT BUTTON SW1 will in some menus increase the value by 1 In other menus the value shown is set to 0 if you press the LEFT BUTTON SW1 An overview of these choices can be seen in the colu...

Страница 5: ...val Since the Service interval in number of door cycles is set in menu d07 one needs to reset d04 at service Since the Service interval in operating time is set in menu d08 one needs to reset d06 at s...

Страница 6: ...p of CDM9 operator Refresh No d0C Shows the active door errors with highest priority first 1 No d0d Set functionality of Auto close timer No C card 0 Close the door and retracts the shelter 1 Close th...

Страница 7: ...o 1 6 3 and 1 6 4 Remember that it is only possible to reset the trip meter and not the total counter or Odometer 8 Now one may change the service interval if there is a need for another interval than...

Страница 8: ...eveller shelter or the door B Press LEFT BUTTON SW1 3 times menu d is showed Select Door submenu by RIGHT BUTTON SW2 d01 is showed C Press SW1 several times until submenu d07 or d08 see Table 1 is sho...

Страница 9: ...d01 is showed C Press SW1 several times until submenu d04 is showed Select the submenu by RIGHT BUTTON SW2 The display now shows the number of cycles that is stored for example 99 D Press the LEFT BU...

Страница 10: ...01 is showed C Press SW1 several times until submenu d0C is showed Select the submenu by RIGHT BUTTON SW2 The display now shows the error with the highest priority D Press the LEFT BUTTON SW1 to see n...

Страница 11: ...the control box in immediate proximity to the connection blocks In order to prevent the components from being destroyed by static electricity during installation or service work any staff coming into...

Страница 12: ...rmation about errors that recently appeared on the leveller While troubleshooting the leveller you can find important information in this menu If you need to contact CPAB helpdesk regarding the contro...

Страница 13: ...6 2A 6 8A 7 4A 8 0A 8 6A 9 2A 1 Yes L13 Cross traffic switch S6 exist or not U00 Cross traffic switch installed U01 No switch installed door located behind leveller default 1 Yes L14 Lift swing lip e...

Страница 14: ...shelter open door U01 Close door stop shelter U02 Open door outside U03 Autoclose of door on off U04 doors extra safety default U05 Close door U06 Open door open in the lid disconnected 1 Yes L26 The...

Страница 15: ...1 and save The functions are now as pre set from factory 1 Yes Table 2 Functions SHELTER menu SW1 Save S01 Show the total number of shelter cycles x1 Refresh No S02 Shelter type default SIR U00 SIR U0...

Страница 16: ...the trip meter and not the total counter or Odometer It is also possibly to do a total service reset via submenu L20 which is explained in detail in 2 2 5 8 Now one may change the service interval if...

Страница 17: ...L is showed Enter Leveller submenu by RIGHT BUTTON SW2 L01 is showed C Press SW1 several times until submenu L06 or L07 see Table 1 is showed Enter for example the submenu L06 by RIGHT BUTTON SW2 the...

Страница 18: ...it from service menu Alternatively press LEFT BUTTON SW1 continuously for 2sec to exit from service menu G The display now goes back to normal operation showing the state of the leveller shelter or th...

Страница 19: ...error in the RAM memory area on the Leveller board has been detected The error is considered as a fatal error and the entire system will be halted until the power supply has been switched off F10 Fau...

Страница 20: ...t from service menu N The display now goes back to normal operation showing the state of the leveller shelter or the door Alternatively the display showing active error codes 2 4 Indication of time fo...

Страница 21: ...ress LEFT BUTTON SW1 continuously for 2sec to exit from service menu F The display now goes back to normal operation showing the state of the leveller shelter or the door 3 1 2 Set Shelter type A The...

Страница 22: ...ton S8 OPEN DOOR S00 will be displayed for 2 sec and winter mode is selected Function to summer mode Shelter function disabled The Leveller in resting position door closed and the shelter switched off...

Страница 23: ...the control box in immediate proximity to the connection blocks In order to prevent the components from being destroyed by static electricity during installation or service work any staff coming into...

Отзывы: