53
MYDENS
COSMOGAS
7 - USE
Err 51
Supply sensor circuit 2
(1005) open
Check that the electric resistance of the sensor
matches the graphics in chapter 8.22. Check the
electric cables for connection between the sensor
and the command board.
If the electric resistance does not match, replace it.
The electric circuit must be repaired if it is damaged.
Without either of the two previous cases, replace the
command and control board.
Err 52
Domestic hot water inlet
sensor 2 circuit (1002)
open
Check that the electric resistance of the sensor
matches the graphics in chapter 8.22. Check the
electric cables for connection between the sensor
and the command board.
If the electric resistance does not match, replace it.
The electric circuit must be repaired if it is damaged.
Without either of the two previous cases, replace the
command and control board.
Err 53
Fumes 1 sensor circuit
(1006) open
Check that the electrical resistance of the fumes
sensor 1006 matches the graphics in chapter 8.22
Check that the wires between the board and the
double fumes sensor are connected correctly
If the sensor does not match, the double fumes
sensor must be replaced.
If the wires are not connected correctly, the connec-
tions must be restored.
Err 54
Fumes 2 sensor circuit
(1014) open
Check that the electrical resistance of the fumes
sensor 1014 matches the graphics in chapter 8.22
Check that the wires between the board and the
double fumes sensor are connected correctly
If the sensor does not match, the double fumes
sensor must be replaced.
If the wires are not connected correctly, the connec-
tions must be restored
Err 55
Not applicable
Err 56
Return sensor circuit
(1007) in short circuit
condition
Check that the electric resistance of the sensor
matches the graphics in chapter 8.22. Check the
electric cables for connection between the sensor
and the command board.
If the electric resistance does not match, replace it.
The electric circuit must be repaired if it is damaged.
Without either of the two previous cases, replace the
command and control board.
Err 57
Supply sensor circuit 1
(1001) in short circuit
condition
Check that the electric resistance of the sensor
matches the graphics in chapter 8.22. Check the
electric cables for connection between the sensor
and the command board.
If the electric resistance does not match, replace it.
The electric circuit must be repaired if it is damaged.
Without either of the two previous cases, replace the
command and control board.
Err 58
Supply sensor circuit 2
(1005) in short circuit
condition
Check that the electric resistance of the sensor
matches the graphics in chapter 8.22. Check the
electric cables for connection between the sensor
and the command board.
If the electric resistance does not match, replace it.
The electric circuit must be repaired if it is damaged.
Without either of the two previous cases, replace the
command and control board..
Err 59
Domestic hot water inlet
sensor circuit (1002) in
short circuit condition
Check that the electric resistance of the sensor
matches the graphics in chapter 8.22. Check the
electric cables for connection between the sensor
and the command board.
If the electric resistance does not match, replace it.
The electric circuit must be repaired if it is damaged.
Without either of the two previous cases, replace the
command and control board.
Err 60
Fumes 1 sensor circuit
(1006) in short circuit
condition
Check that the electrical resistance of the fumes
sensor 1006 matches the graphics in chapter 8.22
Check that the wires between the board and the
double fumes sensor are connected correctly
If the sensor does not match, the double fumes
sensor must be replaced
If the wires are not connected correctly, the connec-
tions must be restored
Err 61
Fumes 2 sensor circuit
(1014) in short circuit
condition
Check that the electrical resistance of the fumes
sensor 1014 matches the graphics in chapter 8.22
Check that the wires between the board and the
double fumes sensor are connected correctly
If the sensor does not match, the double fumes
sensor must be replaced
If the wires are not connected correctly, the connec-
tions must be restored
Err 62
External temperature
sensor circuit (1004) in
short circuit condition
Check that the electric resistance of the sensor
matches the graphics in chapter 8.23. Check the
electric cables for connection between the sensor
and the command board.
If the electric resistance does not match, replace it.
The electric circuit must be repaired if it is damaged.
Without either of the two previous cases, replace the
command and control board.
Err 63
RESET key pressed too
many times in a very
brief period
7.19.3 - Diagnostics: alarms “AttE”
Alarm Description of the alarm
Checks
Solutions
AttE 65 Central heating plant
pressure too low for
more than 10 minutes
Check the pressure switch calibration pressure. FILL
musty appear when the pressure drops below 0.6
bar; check that there are no water leaks from the
central heating plant.
If the pressure switch is not calibrated correctly, it
must be replaced. If the plant has a leak it must be
repaired.
Содержание MYDENS
Страница 67: ...67 MYDENS COSMOGAS 8 MAINTENANCE...
Страница 74: ......
Страница 75: ......
Страница 76: ...COSMOGAS s r l Via L da Vinci 16 47014 MELDOLA FC ITALY info cosmogas com www cosmogas com...