71
MYDENS
COSMOGAS
ATTENTION !!!
The modification of these parameters could cause the appliance, and therefore the plant, to malfunction.
For this reason only a technician that has the awareness and in-depth knowledge of the appliances can modify
them.
To access this menu, introduce the bridge in the board as stated in figure 6.5 detail “A”.
11 - MENU FORCED BY INTERNAL ELECTRIC BRIDGE
Parameter
Description of the parameter
M.U.
Setting range
Factory value
Customised
value
3002
Selection type
From 50 to 55
See Figure 6.7
3012
Domestic hot water operating
mode
/
0 = No domestic hot water;
1 = Indirect water heater with temperature
sensor;
2 = Indirect water heater with thermostat;
3 = Instantaneous with flow switch;
4 = Microaccumulation with two sensors;
5 = Instantaneous with turbine;
model “P” = 5
model “B” = 1
model “C” = 0
3013
Plant fill automatic valve
/
0 = Valve disabled;
2 = Valvola abilitata;
0
3014
Instantaneous domestic hot
water pre-heat
/
OFF = No pre-heat
ON = with pre-heat
OFF
3015
Maximum central heating
temperature
°C
From 20 to 90
80
3016
Minimum central heating
temperature
°C
From 20 to 90
30
3020
Domestic hot water flow rate
sensor
/
0 = B; (MYDENS 15, 24 e 34)
1 = DN 8;
2 = DN 10;
3 = DN 15;
4 = DN 20;
5 = DN 25;
0
3021
2nd Fumes sensor (1014)
/
0 = Disabled;
1 = Enabled;
2 = Enabled with fumes exhaust anti-
closure pressure switch;
1
3022
Central heating minimum
pressure
bar
OFF... 0,3 to 5,1;
0,5
3033
Modulating pump
/
0 = Disabled;
1 = Enabled;
From 4 to 10 = Fixed speeds from 40% to
100%;
0
3034
Modulating pump delta T target
°C
From 5 to 40
15
3035
No function
/
/
/
3036
No function
/
/
/
3052
No function
/
/
/