Error
Error description
Checks
Solutions
Err 67
Grounding error
Make sure the appliance is correctly grounded.
Restore correct appliance grounding.
Err 68
Watchdog communica-
tion error
Replace the command and control board
Err 72
Supply sensor open
Make sure the sensor electrical resistance matches
with the graphic in section 15.14.
If the sensor does not match, it must be replaced.
Exchanger malfunction
Check that the primary heat exchanger temperature
fuse has not intervened.
If the primary heat exchanger temperature fuse has
intervened (the contact is open), the exchanger must
be replaced
Err 73
Return sensor open
Make sure the sensor electrical resistance matches
with the graphic in section 15.14.
If the sensor does not match, it must be replaced.
Err 76
D.H.W. sensor open
Make sure the sensor electrical resistance matches
with the graphic in section 15.14.
If the sensor does not match, it must be replaced.
Err 80
Supply sensor in short
circuit
Make sure the sensor electrical resistance matches
with the graphic in section 15.14.
If the sensor does not match, it must be replaced.
Err 81
Return sensor in short
circuit
Make sure the sensor electrical resistance matches
with the graphic in section 15.14.
If the sensor does not match, it must be replaced.
Err 84
D.H.W. sensor in short
circuit
Make sure the sensor electrical resistance matches
with the graphic in section 15.14.
If the sensor does not match, it must be replaced.
Err 86
Flue exhaust sensor in
short circuit
Make sure the sensor electrical resistance matches
with the graphic in section 15.14.
If the sensor does not match, it must be replaced.
Err 87
RESET key error
RESET key pressed too many times in 60 seconds
Err 93
Appliance selection error Check the 3000 parameters list (section 17)
Err 107
Software error inside
command board
Replace the command and control board
Err 108
Software error inside
command board
Replace the command and control board
Err 109
Error to burner 2, 3 or 4 When burner 1 (MASTER) locks up, it stops burners 2,
3 and 4 with error 109
Solve the error to burner 1 (MASTER).
Err 110
Flapper valve not open
error
Check for and, if necessary, remove any obstruc-
tions in the air intake and flue exhaust ducts;
Check the flapper valve (part 31 fig 3-2)
Err 111
Flapper valve not closed
error
Check the flapper valve (part 31 fig 3-2)
Err 112
Flapper inlet error
Make sure parameter 3005 is set to 0 or 4
If parameter 3005 is 0 or 4, replace the command
board.
Err 113
Software error inside
command board
Replace the command and control board
Err 114
Water flow rate too low
Check the flow rate to the burner (parameter 1062),
it must be greater than parameter 3035.
Increase the water flow rate to the system;
Check for and, if necessary, remove any obstruc-
tions from the system.
Err 115
Master board error
Reset via parameter 3013.
Err 116
(*)
Communication error
BUS communication interrupted
Check the BUS connection.
A burner is not powered
Restore power to all the burners
NO CONN
Microprocessor locked
up
Make sure that the pressure measuring device wires
are not short circuiting
If it is not short circuiting, replace the pressure
measuring device (or disconnect it via menu 3000).
Make sure that the supply measuring device wires
are not short circuiting
If it is not short circuiting, replace the supply measur-
ing device (or disconnect it via menu 3000).
Make sure the display is connected to the
MASTER
If the display is not connected to the MASTER it
shows “NO-CONN”.
If it is none of the above cases, replace the control
board and/or the display.
* This error locks up all burners