8 - INSTALLATION -
Plumbing
8.3 - Temperature and
pressure Relief valve
This appliance is supplied with a Safety Temperature and
Pressure Relief valve which discharge connection must be
piped to prevent scalding in the event of a discharge.
Discharge pipework from the safety valve should be installed
in accordance with building regulations and should contain a
tundish within 600 mm of the outlet of the safety valve.
WARNING !!! Failure to properly pipe the relief
valve discharge can result in scalding of individuals and
animals.
WARNING !!! Never block the outlet of the safety
relief valve or an explosion causing extensive property
damage, severe personal injury or death!
WARNING !!! Never install any type of valve
between the appliance and the relief valve or an explosion
causing extensive property damage, severe personal
injury or death may occur!
If the relief valve discharges periodically, this may be due
to thermal expansion. Contact the water supplier or local
plumbing inspector on how to correct this situation. Do not
plug the relief valve.
Key of Figure 8-1
E = Safety Temperature and Pressure relief valve
F = Not present in this product
G = Elbow (Field supplied)
H = Relief valve discharge piping (Field supplied)
L = Hot water outlet
M = Water intlet
N = Gasket (Factory supplied)
P = Pipe (Factory supplied)
R = Condensate drain
S = Nut (Factory supplied)
L
M
N
R
N
E
F
S
E
F
S
H
P
G
P
H
G
L
M
N
R
N
E
F
S
E
F
S
H
P
G
P
H
G
020022.01.004
Figure 8-1 Piping of the P-T relief valve discharge
and water connections