48
COSMOGAS
AGUAPLUS
14 - USE
14.8 - “User menu”
Pressing the RESET key for 2 seconds accesses the “user
menu”. Display “M” in figure 14-1 begins to show parameter
1001
to tell the user that the mode has changed.
Using the
q
and
p
keys, you can scroll through the
parameters in the menu.
To exit the menu, simply press the RESET key again for 2
seconds.
If no keys are pressed for more than 60 seconds, it
automatically exits the menu.
For models from 100 to 140, all the parameters indicated as
“Burner 1” refer to the appliance Master Burner. To display the
same parameters for the other burners, you must connect the
display to the burner in question as described in section 15.8.
The following parameters can be accessed in this menu:
Parameter
Parameter description
U.M.
1001
Burner 1 - Water supply temperature
°C
1002
Hot water storage tank temperature (N/A)
°C
1004
External temperature (N/A)
°C
1006
Burner 1 - Flue gas temperature
°C
1007
Burner 1 - Return temperature
°C
1008
Burner 1 - Ionisation current
uA
1009
Burner 1 - Main circuit pump and motorised valve status
ON/OFF
1010
Heating circuit pump status (N/A)
ON/OFF
1011
Domestic hot water circuit pump status (N/A)
ON/OFF
1012
Calculated heating setpoint (N/A)
°C
1040
Burner 1 - Current fan rotation speed
rpm
1041
Burner 1 - Fan rotation speed at ignition
rpm
1042
Burner 1 - Fan rotation speed at minimum output heat
rpm
1043
Burner 1 - Fan rotation speed at maximum output heat
rpm
1051
Burner 1 - Last recorded lock-up (Loc) (see section 14.10.1) **
/
1052
Burner 1 - Last recorded error (Err) (see section 14.10.2) **
/
1053
Burner 1 - Number of times the burner lost its flame
no.
1055
Burner 1 - Number of failed burner ignitions
no.
1056
Burner 1 - Number of hours worked
h x 10
1057
Burner 1 - Number of hours worked in domestic water with hot water storage tank
h x 10
1059
*
interval of time between the last two
lockouts (Loc)
1
value in minutes;
2
value in hours;
3
value in days;
4
value in weeks;
1060
*
interval of time between the last two
errors (Err)
1062
Burner 1 - Water flow rate
l/min
1101
Multi-burner: Number of burners on
no.
1102
Multi-burner: Manifold temperature
°C
1103
Multi-burner: Number of burners locked (Loc)
no.
1104
Multi-burner: Number of burners in Error (Err)
no.
1106
Multi-burner: Appliance in emergency
Yes/No
1107
Multi-burner: Calculated heating setpoint
(only for 100, 115 and 140 models) (see Parameter 1012 for the other models)
°C
1120
Multi-burner: Burner 1 modulation level
%
1121
Multi-burner: Burner 2 modulation level
%
1122
Multi-burner: Burner 3 modulation level (N/A)
%
1123
Multi-burner: Burner 4 modulation level (N/A)
%
*
How to read the values of parameters 1059 and 1060:
e.g.: If it shows 1:29, it means 29 minutes;
e.g.: If it shows 2:12, it means 12 hours;
e.g.: If it shows 3:15, it means 15 days;
e.g.: If it shows 4:26, it means 26 weeks.
**
When the number 255 is displayed, it means there was no
lock-up or error.