17 - FORCED MENU
Parameters
Ref.
Parameter description
Adjustment range
D e f a u l t
value
Individual
burner
(mod. 60
and 70)
Burner 1
(Master)
(mod. 100,
115 and
140)
Burner 2
(mod. 100,
115 and
140)
Customised
values
3001 Burner operation address
0 = Not in cascade
1 = Burner 1 (Master),
2 to 4 = Burner from 2 to 4 (slave
burners)
2
1
1
2
3002 Fan adjustment range
from 0 to 4
0
60 = 0
70 = 2
100 and 115 = 0
140 = 2
3003 Display unit of measurement
C = °C and bar;
F = °F and PSI;
C
C
C
C
3004 Water pressure switch
0 = Disabled; 1 = Enabled;
2 = N/A; 3 = N/A
1
1
1
0
3005
Burner flapper valve
0 = Disabled; 4 = Enabled;
8 = N/A; 12 = N/A
4
0
4
4
3006
Water flow rate sensor
0 = Disabled; 16 = N/A;
32 = N/A; 48 = Enabled
48
48
48
48
3007 Condensate level sensor
EnAb = Enabled;
dISA = Disabled
Enab
Enab
Enab
dISA
3008 Combustion gas sensor type
SEnS = Sensor; StCH = Switch
SEnS
SEnS
SEnS
SEnS
3009 External sensor type
10 = 10kohms; 12 = 12kohms;
10
10
10
10
3010 Other sensor type
10 = 10kohms; 12 = 12kohms;
10
10
10
10
3011
pump mode
0 = main c pump; 1 = N/A;
2 = N/A; 3 = N/A;
0
0
0
0
3012 domestic hot water operating mode
0 = only heating;
1= hot water storage tank;
2 = hot water tank with thermostat;
3 = N/A; 4 = N/A; 5 = N/A
0
0
0
0
3013 Reset Err 115
EnAb = Enabled;
dISA = Disabled
Enab
Enab
Enab
Enab
3015 Climatic adjustment: heating supply maximum
temperature (this parameter is overwritten by
parameter 3017)
from 20°C to 90°C
82°C
N/A
N/A
N/A
3016 Climatic adjustment: heating supply minimum
temperature
from 20°C to 90°C
20°C
N/A
N/A
N/A
3017 Supply maximum temperature (this parameter
takes priority with respect to parameter 3015)
from 20°C to 90°C
60°C
60°C
60°C
60°C
3018 Minimum supply temperature
from 20°C to 90°C
20°C
20°C
20°C
20°C
3020
Water flow rate sensor type
0 = N/A; 1 = DN8;
2 = DN 10; 3 = DN 15;
4 = DN 20; 5 = DN 25
4
4
4
4
3022 Minimum water pressure
from 0 to 5 bar
1
1
1
1
3035
Minimum water flow rate
from 0 to 100 l/min
45
60 = 40
70 = 45
100 e 115
= 40
140 = 45
100 e 115
= 40
140 = 45
3050 Slave burner number
from 0 to 3
3
0
1
3
3085 Modbus address
0 to 126
1
1
1
1
3086 Number of Stopbits
1 or 2
1
1
1
1
3100 Material selection
ABS; CPVC; PVC; SST; PP.
PVC
PVC
PVC
PVC
3101 Nation Selection
US, CA
US
US
US
US
Switch
“S4”
Switch “S4” position (see fig 15-11 and 15-12)
On or Off
On
On
On
Off
N/A = Not Applicable