13.2 - General warnings on gas supply
For first start-up of the appliance carry out the following
checks:
That it is powered by the type of fuel for which it is set up
(see section 13.3).
That the gas supply pressure (with the appliance on and
off) falls between the maximum and minimum values
shown in the table in section 16.
That the gas supply system is provided with all the
safety devices and controls required under current
national and local codes.
That the flue gas outlet terminal and the combustion air
intake terminal are properly connected and free from any
obstruction.
That the flue gas outlet terminal and the combustion air
intake terminal are located outside the building.
That the condensate drain is properly connected.
WARNING !!! It is forbidden to supply
the appliance with a type of gas other than those
anticipated.
WARNING !!! Ensure that the supply pressure
and gas are the ones for which the appliance is set.
The appliance is provided with the relevant gas conversion kit.
Before installation it is recommended that the inside of the
gas adduction pipe be cleaned thoroughly.
A shut-off manual valve must always be installed on the
gas adduction pipe.
To avoid damage to the appliance gas control assembly,
carry out the seal test at a pressure of not more than 50
mbar.
If the test of the gas system has to be carried out at
pressures greater than 50 mbar, turn off the manual gas
shut-off valve located immediately up-stream he appliance,
to isolate it from the system.
In Figure 7-1 you can check the position of gas connection.
The sections of piping that make up the gas adduction
system must always ensure sufficient gas supply to cover
the maximum required.
WARNING!!!
If you smell gas:
A - Do not try to light any appliance.
B - Do not touch any electrical switch. Do not use any
phone in your building.
C - Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
D - If you cannot reach your gas supplier, call the fire
department.
13.3 - Confirm the appliance gas type
The type of gas and the gas supply pressure that the appliance
is set up for is listed on the rating plate.
The appliance can operate using one of the following two
gases:
2H-G20-20mbar NATURAL GAS
means the appliance is regulated to work with type H
second family gas (NATURAL GAS) at a supply pressure of
20 mbar.
3P-G31-37mbar LP Gas
means the appliance is regulated to work with type P third
family gas (propane, also known as LP gas) at a supply
pressure of 37 mbar.