31
AGUAPLUS
COSMOGAS
11 - INSTALLATION - Air intake and flue exhaust ducts
11.1.2 - Flue exhaust
The appliance is standard supplied with fittings to connect to the
flue exhaust. To install, proceed as shown in figure 11-2.
1.- put duct “E” into reducer “C”, being sure that the gasket in
reducer “C” is positioned correctly;
It is mandatory to install polypropylene ducts that are more
resistant to condensate formation on the “B” flue exhaust side.
Take particular care in installing the ducts in the parts that cross
the wall towards the outside; it must always be possible to do
normal maintenance operations. Therefore, install the pipes in a
sheath in order to be able to slide them out.
The horizontal sections must always have a slope of at least 2%
towards the condensate drain devices.
The appliance is already equipped with a condensate collector,
which must be joined to an exhaust pipe (see section 9).
WARNING !!! This condensate drain is designed to
make all the liquid produced by an individual appliance flow
out. Should several appliances be installed, provide each with
its own condensate drain.
The flue exhaust system can be extended up to a maximum
distance as instructed in section 16. Each 90° curve has a loss
equivalent to what is described in section 16.
WARNING !!! The flue exhaust outlet must be
appropriately protected against the effects of the wind.
WARNING !!! Mechanically secure the joints between
the various exhaust duct components using fixing or
equivalent systems. See figure 11-4.
WARNING !!! The temperature of the exhaust pipe
during operation can reach 90°C. If they cross through walls
that are sensitive to these temperatures, put in a protective
heat insulating sheath.
WARNING !!! The exhaust ducts must be appropriately
supported via rigid brackets positioned no more than 1 m from
each other. The brackets must be secured to rigid walls that
can support the weight of the duct itself.
WARNING! The table below shows the equivalent
lengths of the exhaust components:
TABLE OF EQUIVALENT LENGTH COMPONENTS
CODE
DESCRIPTION
UM = equivalent linear meters
60T-140T
62617344
PIPE 1m Ø110
1,0
62617345 ELBOW 45° Ø110
2,2
62617346 ELBOW 90° Ø110
4,0
62617289
PIPE 1m Ø160
/
62617297 ELBOW 45° Ø160
/
62617298 ELBOW 90° Ø160
/
Figure 11-4 - Securing exhaust ducts
Figure 11-2 - Split system installation
Figure 11-3 - Assembled system
C
F
E
020014.01.028
Air Inlet
Flue
gas outlet
N
M
020014.01.029
Air Inlet
Flue
gas outlet