File : CS-SUP-MUTI-WTHERMAPP-E01.sxw
6.1.5 Definition of the module control bytes
➢
Definition of the
Operating Mode
byte (0x01) :
MSB
LSB
Operanting Mode
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
-
Threshold
Detection Mode
0
: successive mode
1
: cumulative mode
Low Threshold
Detection
0
: deactivated
1
: activated
High Threshold
Detection
0
: deactivated
1
: activated
Datalogging
00
: deactivated
01
: time steps
10
: once a week
11
: once a month
Stop Mode of the
Datalogging
0 :
permanent loop
1 :
stop memory full
-
Attention, it is advised the greatest prudence when modifying the parameter setting of the
Operation
Mode
variable. Indeed, the modifications on this variable generally requires the update of the associated
parameters.
Defautl value :
WaveTherm – DALLAS :
0x0A
WaveTherm – PT100 :
0x08
WaveTherm – PT1000 :
0x08
➢
Definition of the
Application Status
byte (0x20) :
It is possible to reinitialize to zero the bits by a write to the
Application Status
parameter.
MSB
LSB
Application Status
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reset
detection
0:
not
detected
1:
detected
Low
Threshold of
sensor 2
0:
not
detected
1
: detected
High
Threshold of
sensor 2
0:
not
detected
1
: detected
Low
Threshold of
sensor 1
0:
not
detected
1
: detected
High
Threshold of
sensor 1
0:
not
detected
1
: detected
number of detected
sensors
0 :
0 or 1 sensor
detected
1 :
2 sensors detected
-
End of
battery life
0:
not
detected
1
: detected
➢
Definition of the
Extended Application Status
byte (0x21) :
MSB
LSB
Extended Application Status
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
-
-
-
-
-
-
Probe fault on
sensor 2
0:
not detected
1
: detected
Probe fault on
sensor 1
0:
not detected
1
: detected
Remark : The probe fault bits are set only when a problem is detected on WaveTherm – PT100, and
WaveTherm – PT1000 probes.
WaveTherm modules – application handbook
page 24 of 65