File : CS-SUP-MUTI-WTHERMAPP-E01.sxw
➢
Format of access for parameter (s) writing
Contents of request REQ_SEND_FRAME
Data field (max : 152 bytes)
Applicative
command
Number of
parameters
read
Number of
the 1
st
parameter
Size of the
1
st
parameter
Data of the
1
st
parameter
...
Number
of the n
th
parameter
Size of the
n
th
parameter
Data of
the n
th
parameter
1 byte
1 byte
1 byte
1 byte
variable
...
1 byte
1 byte
variable
n
max
= 9
Contents of response RECEIVED_FRAME
Data Field (max : 152 bytes)
Acknowledgement
of the applicative
command
Number of
parameters
written
Number of
the 1
st
parameter
Update Status
Number of the
2
nd
parameter
Update Status
...
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
...
'Update Status' :
0x00 : update OK
0xFF : update error
Attention, some of the parameters are limited, i.e. their values should not be written out of the limits.
If a value is written out of the limits, the value will be written but not managed, the status of writing will be
OK.
Example: parameter 0x04 (hour of the first time-window) this parameter is set up from 0 to 23. Thus if
value 40 is set, it will be written, but is not managed by the system.