The time windows function as follows,
Set the start time for the first time window and its wake-up period ;
Set the start time for the second time window and its wake-up period ;
Select the days of the week during which the time windows are enabled ;
'Enable time windows by day of the week' = 0x7F
Validate the time window mode with the 'wake-up system status word'.
'Wake-up system status word' = 0x01
Note: The format of the parameters 'Start time for time windows' is expressed in hour, and its value
lies between 0 and 23.
For example, if the start time of time windows at 12h00; the value 0x0C should be configured.
The format of the wake-up periods of each time windows, is the same one as the default wake-up
period; i.e. it is expressed in seconds, and cannot exceed value 0x0A.
The format of the applicatives commands for reading and writing internal parameters, is described in chapter
6.2.
Enable time windows by day of week
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
-
Sunday
0 : enabled
1 : disabled
Saturday
0 : enabled
1 : disabled
Friday
0 : enabled
1 : disabled
Thursday
0 : enabled
1 : disabled
Wednesday
0 : enabled
1 : disabled
Tuesday
0 : enabled
1 : disabled
Monday
0 : enabled
1 : disabled
Attention, the coding of each bit is reversed, compared to the parameter ' Enable wake-up periods
by day of the week'.