Mounting and Operating Manual
Central Battery System EURO ZB.1
64
CEAG Notlichtsysteme GmbH
TLS-Input (0=Off)
01
-------------------------------
+ -
OK
TLS
SKU
1x6A
BGT:1 SKU1 out.circ. 1
Slot not active
-------------------------------
+ -
OK
BGT: 2 SKU4 out.circ.1
Type: SKU 1x6__
-------------------------------
+ -
OK
Non-permanent light ?
No
-------------------------------
Yes No
OK
Permanent light ?
No
-------------------------------
Yes No
OK
Timer -1
No
-------------------------------
Yes No
OK
Timer -2
No
-------------------------------
Yes No
OK
Control
Unit
H:M:S
T.M.J
U= 242,2 V I=+5,2 A
Operation
Mains=222,3 V
Programming:
1
Progr. contr. unit
-------------------------------
Programming:
2
Progr. charger
-------------------------------
Programming:
4
Programming TLS
-------------------------------
Programming:
5
Teach. curr. values
-------------------------------
Programming:
End
-------------------------------
Programming:
3
Programming SKU
-------------------------------
DLS/SDS-On
1
(0=Off)
01
-------------------------------
+ -
OK
DLS/SDS-On
2
(0=Off)
00
-------------------------------
+ -
OK
By a further example given here it shall be
explained how the factory setting of a circuit
switching variant can be changed from perma-
nent to staircase lighting operation. A total of
32 input channels can be assigned.
Example:
The circuit module 1 x 6 A (SKU 1 x 6 A.1)
on Slot 4 of subrack 2 shall be reprogrammed
from permanent light to staircase lighting
mode. To enable the circuits to be switched via
external switching functions in mains operating
mode a circuit TLS module (subrack 1 slot 7)
must be installed in the system as an option.
A total of 32 inputs can be assigned through
the options DLS (permanent light switch chek-
king function), TLS (staircase light switching
system). Each module has 8 input channels
(max.).
Care must be taken during programming that
the 32 inputs are assigned consecutively.
Example:
The first module is a DLS. The second module
is a TLS. Taking this example inputs 1 through
8 would be assigned to the DLS module. The 8
input channels of the TLS module would then
be assigned to inputs 9 through 16.
Enter „No“ for switching
variants non-permantent
light, permanent light, ti-
mer 1, timer 2, DLS input
1 and DLS input 2 and
press OK to confirm.
Use the plus button to
select the input channel
via which the circuit is to
be controlled.
Via input channel 1 of the TLS (Item 1) circuit 1
of circuit module 6 on subrack 2 in mains and
battery operating mode shall be switched for a
time span ranging between 1 and 15 minutes.
The assignment is effected via the freely pro-
grammable control unit.
Press the menu button on the control unit for
> 5 sec.
Use arrow button to select programming item 3.
Press the + button to select the circuit that shall
be programmed.
In this example it is circuit 1 of circuit module 1
x 6 A on slot 6 of subrack 2 (see figure).
22
Programming Final Circuits to Staircase Lighting (TLS)
Programming the System
The TLS staircase lighting function has a total
of 8 input channels. For power supply to the
glow lamps in the illuminated buttons 0.05 A is
available per input channel. The assignment,
ie. which circuit of the safety lighting system is
to be switched via this input channel, can be
freely selected with the help of the control unit.
The programming steps necessary for this can
be seen from the flow chart.
1
Max. current deviation
10%
-------------------------------
+ -
OK
Note: Current setpoint
Teach new value!!!!
-------------------------------
OK
Circuit monitoring ?
Yes
-------------------------------
Yes
No
OK