Additional features:
External 24 V
– 20 W continuous rating
– Output via front-side plug
– Voltage electrically isolated
Internal 24 V
– 100 W continuous rating
– 140 W Peak rating (20 msec.)
– Feeding a maximum of 26 SKU
Connection in parallel
possible for several converters!
Feed-in via AC/AC converter
possible to enable external mains
supply.
This module supplies 24 V- and 6 V direct
voltage to the central battery system.
Light-emitting diodes
LED „24 V extern“
This LED lights up if an external 24-V DC
voltage is applied to the „24VDC OUT“
terminals.
LED „24 V intern“
This LED lights up if the internal 24 V
DC voltage is applied to the EURO ZB.1
system.
LED „6 V intern“
LED lights up if the internal 6 V supply
voltage is applied.
Control elements
The button „Service PIN“ is located in the
bore.
5.3.1 AC-Module
This optional unit supplies the central
battery system with an AC-voltage galva-
nically isolated, in mains operation.
Connection to terminals 1~ 2 IN to DC/
DC converter.2.
Attention!
Only the AC-module has to be con-
nected to this terminals.
Modules
5.3
Functions of the DC/DC converter.2
1
2
3
4
5
1: Feed for optional AC module
2: LED „24 V extern“
3: LED „24 V intern“
4: LED „6 V intern“
5:
Bore with „Service PIN“ but-
ton