Mounting and Operating Manual
Central Battery System EURO ZB.1
14
CEAG Notlichtsysteme GmbH
Substation EURO US.1
EURO US.1/72
EURO US.1/42
Rated operating voltage:
----------- 230 V 50/60 Hz -------------
Control unit ST 20 E
1
1
DC/DC converter (model DC/DC.2)
1 - 2
1
Circuit module SKU
0 - 36
1
)
0 - 21
Outgoing distributor/ circuits (optional) none
none
Dimensions (mm)
W 800
600
H 2050
1200
D 400
300
plus optional base (mm)
H 100 / 200
300
Weight (depends on components mounted)
upon request
Adm. system temperature ranges:
storage
-20 °C to + 40 °C
operation
-5 °C bis + 35 °C
Batteries:
--------------------------------------------
Enclosure type as per DIN EN 60 529 IP 21
IP 54
Prot. class as per DIN EN 60 598
1
1
3-phase system division
no
no
Cable entry
at top/bottom possible
yes / yes
yes / no
Conductor size
2
)
Battery and mains lead
up to 35 mm
2
35 mm
2
Outgoing distributor
up to
–
–
Final circuits
up to
2,5 mm
2
2,5 mm
2
Control unit ST 20 E
up to 2.5 mm
2
conductor size
Battery and mains power supply
via outgoing distributor in a
EURO ZB.1 control cabinet
1
) One DC/DC.2 converter can supply operating voltage to a max. of 26 modules;
for more than 26 modules an additional DC/DC.2 converter must be installed.
2
) Conductor sizes of the connecting leads must be selected to suit the type of
mains power supply and requirements of the consumer circuits in line with the
applicable regulations and standards (ruling at the operating location of the plant).
Technical Data
Fig.11: Inside view of EURO US.1/72
Fig.12: Cable entries are prepunched
(other types, eg. sponge rubber, are
available on request)
1 = M40/M32
2 = M32
3 = M16
4 = M20/M25
1
3
2
3
4
4