![Cooper safety CEAG EURO US.1 Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/cooper-safety/ceag-euro-us-1/ceag-euro-us-1_mounting-and-operating-instructions_2664639006.webp)
Mounting and Operating Manual
Central Battery System EURO ZB.1
6
CEAG Notlichtsysteme GmbH
Fig. 1: EURO ZB.1 of type EURO
ZB.1/200S and for operation with a
battery capacity of up to 240 Ah and
up to 26 SKU modules
Fig. 2: EURO ZB.1 of type ZB 96/ LAD
for operation with battery capacities
of up to 240 Ah and up to 10 charging
modules CM 3.4 A.
This unit is capable of powering up to
15 type EURO US.1 substations with
230 V mains and battery power.
To suit local conditions a number of diffe-
rent system configurations are employed.
These standardized configurations are
identified, for example, as follows:
EURO ZB.1/52
To operate max. 26 circuit modules type
SKU. Up to 6 substations EURO US.1
can be supplied with battery and mains
power (up to 6 substations, single-
phase).
ZB 96/LAD
These are designed as charging and
monitoring units for the mains and
battery power supply of a greater number
of substations type EURO US.1. Up to
two SKU modules can be energized and
controlled.
EURO ZB.1/20K, EURO ZB.1/188K
Designed (as regards dimensions) to
be operated in conjunction with CEAG
compact battery cabinets (max. 10 or 18
SKU modules).
EURO US.1/72 oder EURO US.1/26
Designed as substations for operation
with max. 36, 13 etc. circuit modules
types SKU to perform only control and
monitoring tasks for subsystems of the
lighting equipment.
These substations do not provide for
charging means for the connected batte-
ry emergency supply ; the battery and
mains power supply is effected via the
EURO ZB.1 system.
What is included in this manual also
applies analogously to the EURO US.1
configurations listed under «3 Technical
Data».
For emergency power supply CEAG
battery cabinets or racks are employ-
ed. The storage capacity of the battery
banks to be connected (battery cabinets
or racks) is governed, inter alia, by the
available charging capacity (see configu-
rations listed under«3 Technical Data»).
Notes:
Planning and design information
can be seen from the CEAG catalog
„Safety Luminaires and Safety Ligh-
ting Systems“ as amended under
catchwords / chapters such as:
– Equipment Overview / Techni-
cal Data
– Planning
– Equipment Possibilities
– Inquiry Texts
Under the heading «Compon-
ents and Options» brief characte-
ricts, technical data and ordering
numbers for modules and sup-
plements can be found that may
be operated via a EURO ZB.1 or
EURO US.1 system.
Moreover, CEAG offers con-
sultation and training services for
planning, set-up and operation of
lighting systems comprising the
EURO ZB.1 system.
For relevant information please
visit our website www.ceag.de.
A EURO ZB.1 system supplies and moni-
tors lighting /emergency lighting circuits
comprising luminaires and electronic
ballasts included in the CEAG Safety Lu-
minaires Program. For emergency power
supply battery cabinets from the CEAL
supply program can be used having a
storage capacity of up to 240 Ah (see
standard cabinet types under „3 Techni-
cal Data“).
Product Description