Mounting and Operating Manual
Central Battery System EURO ZB.1
56
CEAG Notlichtsysteme GmbH
SKUs of final circuits
The circuit changeover modules energize
and monitor safety luminaires with elec-
tronic ballasts for DC operation
.
The Circuit monitoring verifies the correct
functioning of the connected luminaires.
Output voltage for battery operation: 220
V DC
-
Changing over individual emergency
lighting circuits;
-
Freely programming maintained light,
switched maintained light or non-
maintained light;
-
Separate fuse protection for mains
and battery operation (two pole)
-
Fuses (1) on front of the modules
easily accessible;
-
In case of one-pole ground leakage
during AC operation DC operation
may continue without problems
-
LED indications (2) for failure and
operation „EIN/On“ for each circuit;
Log printer
The printer can be mounted on the sub-
rack BGT1, controlled and logged on or
off via the control software of the
ST 20 E (eg. when paper rolls or printer
ribbons must be replaced and require the
printer to removed /replaced).
Fig. 49: SKUs for final circuits