Mounting and Operating Manual
Central Battery System EURO ZB.1
29
CEAG Notlichtsysteme GmbH
Application:
Installation in the EURO ZB.1
(EURO US.1) control cabinet
to facilitate maintenance efforts
Notes:
Please observe info on bus
technology and shielding as de-
tailed on the following pages.
As regards planning and use of
the module please refer to the tech-
nical documentation supplied with
the modules and brochures and
leaflets of CEAG Notlicht-systeme
GmbH.
1 2 3 4
Item 1: top terminal strip for (moni-
toring) inputs
Item 2: bottom terminal strip
Item 3: Indicating LEDs
LEDs 1 ... 8 light up if the circuit is
closed or the monitored supply volta-
ge is applied, LED
„S
törung
/
Failure“
lights up if a fault is detected in the
module
Item 4: Fixing element (fastening
screw) for the module.
Modules
5.13
Functions of Permanent Light Switch Checking
DLS
Description
This electronic monitoring module serves
for (light) switch checking purposes.
During mains operation luminaires of the
general and safety lighting systems are
switched in line with switch positions and
adjustments of the EURO ZB.1 control
unit.
During emergency operation (eg. after
monitored phases of the mains power
supply system have failed) the circuits of
the safety lighting system are operated
as per the settings made on the EURO
ZB.1 control unit.
Technical Data
Connection
– Terminals 2.5 mm², rigid and flexible.
Number of light switch inputs
– up to 8, electrically isolated
– Rated voltage U
n
= 230 V