Mounting and Operating Manual
Central Battery System EURO ZB.1
23
CEAG Notlichtsysteme GmbH
Fuses
On the circuit changeover unit’s facepla-
te 8 outgoing fuses 1.6 AT / 250 V are
arranged.
Size of fuses:
6.3 mm x 32 mm, sand-filled.
Attention!
Rated current must not exceed
1 A per circuit!
Control elements
Service-PIN
Adjacent to „Service“ inscription the-
re is a button which must be actuated
for basic programming of the system.
Basic programming is carried out in the
Factory.
Indicating elements
LED „ON“
This LED lights up if voltage is applied to
the outgoing terminals.
LED „Failure“
This LED lights up if current measured
derivates from preset value by x %.
Additional features
Individual monitoring
of a maximum of 20 luminaires
Fuses are easily accessible
Continuous current per circuit
1 A
Making current
60 A/ms
Typical changeover time
AC/DC 200 ms
5.7
Functions of Circuit Changeover SKU 4 x 1 A
Modules
1: Fuses
2: „Service-PIN“ button
3: LED „ON“
4: LED „Failure“
1
2
3
4
1
1,6 A