Introduction
XW-210 WiFi™ Users Manual
1.5 Connectors & Indicators
Relay
The XW-210 has an internal high-current relay. Screw terminals are provided for the
Common, Normally
Open,
and
Normally Closed
contacts of the relay. The screw terminals are internally connected directly to
the relay with no internal fuse or other over-current protection. The relay contacts are isolated from all
other circuits.
Digital Input
The XW-210 has an optically-isolated digital input. The optically-isolated input provides electrical isolation
between the digital input and the low voltage control circuits of the XW-210. The input can be used as a
pulse counter and has a built-in debounce of 20ms.
1-Wire Sensor Bus
The XW-210 works with “1-wire” digital temperature and other Xytronix 1-wire sensors. The sensors are
available in several configurations, are interchangeable and require no calibration. The sensors require
three connections for communications and power (+5V, Gnd, Data). Control relays or trigger email
messages based upon temperature and other sensor values.
Power Supply
The XW-210 employs modern switch-mode power supply which works from 9 to 28VDC. With this type
of power supply the current draw decreases as the voltage increases. The power supply voltage (+Vin) is
monitored internally and can be logged.
LED Indicators
Power
: Illuminated whenever the module is powered
Relay
: Illuminated whenever the relay is energized
Input
: Illuminated when a sufficient voltage is applied to the opto-coupler input
Link
:
See table below:
WiFi State
LINK LED
Not connected
Off
WPS in progress
Slow flashing
☼
☼
(1/4Hz)
Access Point mode
Med flashing
☼ ☼ ☼ ☼ ☼ ☼ ☼ ☼
(2Hz)
Connected to network waiting for DHCP
Fast flashing
☼☼☼☼☼☼☼☼☼☼☼☼☼☼☼
Connected to network with static or DHCP
Solid on
☼
Page 6
Xytronix Research & Design, Inc.
Содержание WebRelay Wireless XW-210I