XW-210 WiFi™ Users Manual
6.6.3 XW-210 Full Address Table
The table below gives commonly used function codes, memory types, data sizes, and equivalent PLC
addresses for accessing the XW-210. The data size will be the same regardless of the addressing mode.
Function
Code
Address
(Decimal)
Data Size
PLC Address
Mode 485
PLC Address
Mode 584/984
Read Relay 1
01
0
Discrete
1
1
Write Relay 1
05
0
Discrete
1
1
Read Input 1 State
02
0
Discrete
1001
10001
Read Vin
03
16
32-bit Float
4017
40017
Read Sensor 1
03
272
32-bit Float
4273
40273
Read Sensor 2
03
274
32-bit Float
4275
40275
Read Sensor 3
03
276
32-bit Float
4277
40277
Read Sensor 4
03
278
32-bit Float
4279
40279
Read Counter 1
03
528
32-bit int
4529
40529
Write Multiple Relays
15
0
8-bit
1
1
Pulse Relay
16
784
32-bit Float
4785
40785
Xytronix Research & Design, Inc.
Page 69