Ref.no.: 003274/Revision 2.4 @2019 Control Data Systems Page 32
|
201
Information
, press
Detect Device.
Press
Start
to detect the device and retrieve its current settings
information. Once the fields are populated, the device is ready to be provisioned.
5.3.1
Provisioning
1.
Provide the following:
a.
Network ID (can be found in the VR950’s MCS website, under
WirelessHART
,
Access Point
,
Network ID
– here the value is Hexadecimal and must be transformed into a Decimal value
for use in the
WirelessHART Provisioning Tool
). Press
Set
.
b.
Join Key (can be found in the VR950’s MCS website, under
WirelessHART
,
Access Point
,
App
Join Key
) Press
Set
.
Figure 5.3.4 Network ID and Join Key setup example (the Network ID found in MSC will be 2020 – hexadecimal value)
2.
Press
Modify
and select and provide the suitable values to produce the desired
Burst Message
:
a.
Command:
-
1
– Read Primary Variable
-
2
– Read Loop Current and Percent of Range
-
3
– Read Dynamic Variables and Loop Current
-
9
– Read Device Variables with Status
-
33
– Read Device Variables
-
48
– Read Additional Device Status