8
3. Mounting the steam pipe.
• Remove protective caps from the steam pipe.
• From the inside of the duct push the steam pipe into the valve unit until it comes to a stop (the
resistance of the O-ring inside the valve unit must be overcome). The steam pipe is installed
correctly, if the secondary condensate drain pipe pokes X mm out of the duct (see illustration
and table below).
Note: To improve gliding ability moisten the end of the steam pipe and the O-ring inside the
valve unit with water (do not use oil or grease!).
4. Fix steam pipe.
• Horizontally align steam pipe using a spirit level, then fix the end of the steam pipe to the duct
wall or the duct ceiling (by client).
• Screw M5x6 grub screws (allen key 2.5 mm) provided on both sides into the valve unit, until
they touch the steam pipe.
X
Esco 5
Esco 10
Esco 20
X
30 mm
24 mm
50 mm
Water