5.3.4.2 Bell-shaped float drain for Esco stainless steel versions
• Wrap teflon tape around the thread of the straight fitting or apply silicone-free sealant (heat-
resistant up to 155 °C). Then, remove protective plug from the condensate connector of the valve
unit screw fitting into the valve unit.
• Wrap teflon tape around the thread of the angled screw coupling or apply silicone-free sealant
(heat-resistant up to 155 °C). Then, screw angled screw coupling into the bell-shaped float drain
as shown below (
the union nut must point to the top and the arrow on the bell-shaped float
drain must point in drain direction
).
• Slide angled screw coupling with the bell-shaped float drain onto the straight fitting until it comes
to a stop. Tighten union nut so far, that the bell-shaped float drain can not be turned by hand
anymore.
Rp 1/2"
Wrench size 22 mm
Wrench size 24 mm
Flow direction
wrap teflon tape around the thread or apply silicone-free
sealant (heat-resistant up to 155 °C)