45
Rp 1/2"
5.3
Mounting the primary condensate drain
Important notes
– The primary condensate must be discharged separately from the secondary condensate.
– The primary condensate can either be discharged pressure-free or with a
maximum back-pressure
of 1/2 of the primary steam pressure
. The discharge/feedback of the primary condensate is
customers responsibility.
5.3.1 Thermostatic steam trap for Esco cast-iron and stainless steel versions
wrap teflon tape around the thread or
apply silicone-free sealant
(heat-resistant up to 155 °C)
Wrench size 32 mm
• Wrap teflon tape around the threads of the threaded pipe or apply silicone-free sealant (heat-
resistant up to 155 °C). Then, screw threaded pipe into the primary condensate drain (
arrow on
the condensate drain must point in drain direction
).
• Remove protective plug from the condensate connector of the valve unit, then screw threaded
pipe from the bottom into the valve unit.
Flow direction
admissible
mounting position
not admissible
mounting position