44
5.2
Mounting the secondary condensate drain
Rp 1/2"
Wrench size 22 mm
wrap teflon tape around the thread or
apply silicone-free sealant
(heat-resistant up to 155 °C)
Wrench size 32 mm
Rp 1/2"
Wrench size 19 mm
wrap teflon tape around the thread or
apply silicone-free sealant
(heat-resistant up to 155 °C)
• Wrap teflon tape around the thread of the angled screw coupling or apply silicone-free sealant
(heat-resistant up to 155 °C). Then, screw angled screw coupling into the secondary condensate
drain (
arrow on the thermostatic steam trap must point in drain direction
).
• Slide angled screw coupling onto the condensate pipe until it comes to a stop. Tighten union nut
so far, that the angled screw coupling can not be turned by hand anymore.
• The outlet of the secondary condensate drain must be connected to the drain line of the building
via an open funnel (
pressure-free draining
) with siphon (by client).
Thermostatic steam trap stainless steel
Thermostatic steam trap brass
admissible
mounting position
not admissible
mounting position
5.2.1
admissible
mounting position
not admissible
mounting position