4. Fix collector pipe (illustration below shows DR73 J2A Left Right).
Important
: if the valve unit(s) is(are) not mounted yet, make sure the connector(s) of the collector
pipe poke(s)
exactly
T mm
out of the duct (see table in step 3) before fixing the collector pipe.
• Horizontally align collector pipe using a spirit level, then fix the end of the collector pipe with the
brackets supplied to the duct floor or with the optional wall support to the duct wall.
• Screw the M5x6 grub screws (allen key 2.5 mm) provided on into the flange pipe of the valve
unit, until they touch the steam pipe.