29
5. Mount valve unit.
• Remove protective plug from the valve unit.
• Push valve unit onto the steam pipe until it comes to a stop (the resistance of the O-ring inside
the valve unit must be overcome). Then, fix valve unit to the supporting sheet as shown below
using two screws, washers and nuts each.
Note: To improve the gliding ability moisten the steam connector of the collector pipe and the
O-ring inside the valve unit with water (do not use oil or grease!).
• Screw the M5x6 grub screws (allen key 2.5 mm) provided on both sides into the valve unit (as
shown below), until they touch the steam pipe.
Esco 10
Esco 20
Esco 30
M8 x 35
Wrench size 13 mm
M12 x 35
Wrench size 19 mm
Water