25
The installation site of the steam humidifier depends largely on the location of the steam distributor
(see chapter 5.4). To
ensure
proper functioning
of the steam humidifier and to
obtain an optimal
efficiency
, the following points must be considered and observed when choosing the location for
the steam humidifier:
– Install the steam humidifier so that the
length of the steam
hose is kept as short as possible
(
max. 4 m
) and that the
minimum bend radius (R= 300 mm)
and
up-slope (20 %)
or
down-
slope (5 %)
of the steam hose is observed (see chapter 5.4.5).
– The steam humidifiers Condair EL2 are designed for wall-mounting. Make sure that the construc
-
tion (wall, pillar, floor-mounted console, etc.) to which the humidifiers are to be mounted, offers
a
sufficiently high load-bearing capacity
(take notice of the weight information found in the
dimension sand weights table above), and is suitable for the installation.
CAUTION!
Do
not
mount the steam humidifier directly to the ventilation duct (insufficient stability).
– The back panel of the Condair EL2 is retaining heat during operation (max. surface temperature
of the metal housing approx. 60 - 70 °C). Make sure, therefore, that the construction (wall, pillar,
etc.) to which the units are to be mounted, does not consist of heat-sensitive material.
– Install the steam humidifier in such a manner that it is
freely accessible
with sufficient space
available for maintenance purposes (refer to the above illustration for minimum distances).
– The Condair EL2 is protected according to
IP20
. Make sure the units are installed in a drip-proof
location and the admissible ambient conditions are complied with.
– The steam humidifier Condair EL2 may only be installed in rooms with a floor drain.
CAUTION!
If for some reason the Condair EL2 must be installed in a location without floor drain, it is
mandatory to provide a leakage monitoring device to safely interrupt the water supply in case
of leakage.
– When fixing the Condair EL2 use
only the fixing materials supplied with the unit
. If fixing with
the materials supplied is not possible in your particular case, select a method of fixing that is of
similar stability.
– The Condair EL2 is designed for installation and operation within buildings (admissible temperature
range see chapter 10.1). For outdoor operation the Condair EL2 must be placed in a weather
protective housing. If ambient temperatures near or below the freezing point have to be expected,
the protective housing must equipped with a thermostat controlled heating of sufficient capacity.
The water supply pipe must be equipped with a trace-heating and must be insulated up to the
protective housing.
Содержание EL2
Страница 1: ...Installation and Operating Instructions Electrode Humidifiers 2549892 EN 1112 Condair EL2 ...
Страница 2: ......
Страница 68: ...68 Condair EL2 23 32 32 45 Dimensions in mm ø22 492 670 69 351 180 182 246 180 180 50 547 223 163 118 233 ...
Страница 69: ...69 Notes ...
Страница 70: ...Notes ...
Страница 71: ... Condair Ltd Printed in Switzerland Technical modifications reserved ...