System 3: Supply air humidity control with continuous output limitation
Supply air humidity control (humidity sensor installed in supply air duct) should be used
only where room humidity control is impracticable for technical reasons
. Such systems
always require a PI-controller.
The humidity sensor (A1) is located in the supply air duct after the steam distribution pipe. The
humidity sensor (A2) for the continuous output limitation is located in the supply air duct before
the steam distribution pipe. Such a system requires a PI-controller with the option to connect a
second humidity sensor.
A1/2 humidity sensor
B1 ventilation interlock
B2 airflow monitor
B3 safety humidistat
PI
E
External PI controller
Y
input signal from A1
Z
input signal from A2
Which humidity control system for which application?
Application
Location of the humidity sensor
room or exhaust air duct
supply air duct
Air conditioning systems with:
– supply air portion up to 33%
System 1
System 1
– supply air portion up to 66%
System 1 or 2
System 2 or 3
– supply air portion up to 100%
System 2
System 3
– supply air humidity control
—
System 3
Direct room humidification
System 1
—
Please contact your Condair supplier, if your application meets the following conditions:
– Humidification of small rooms up to 200 m
3
– Air conditioning systems with a high number of air exchanges
– Systems with variable air volume flow
– Test facilities with extreme control accuracy requirements
– Rooms with a high variation in max. steam capacity
– Systems with temperature fluctuations
– Cold rooms and systems with dehumidification
Admissible input signals
– 0...10VDC (external continuous controller)
– 24 V On/Off (humidistat)
Содержание EL2
Страница 1: ...Installation and Operating Instructions Electrode Humidifiers 2549892 EN 1112 Condair EL2 ...
Страница 2: ......
Страница 68: ...68 Condair EL2 23 32 32 45 Dimensions in mm ø22 492 670 69 351 180 182 246 180 180 50 547 223 163 118 233 ...
Страница 69: ...69 Notes ...
Страница 70: ...Notes ...
Страница 71: ... Condair Ltd Printed in Switzerland Technical modifications reserved ...