5.4.5 Installing the steam hose
Important!
Use original Condair steam hose exclusively. Other types of steam hoses can cause
undesired operational malfunctions.
Instructions for the hose layout
The hose layout depends on the position of the steam distribution pipe:
– Steam distribution pipe is mounted
more than 300 mm above the top edge of the humidifier
:
Initially, lead the steam hose with an
upslope of at least 20% over a minimum height of 300
mm
, then lead the hose with a
minimum upslope of 20%
and/or a
minimum downslope of
5%
to the steam distribution pipe.
– Steam distribution pipe is mounted
less than 300 mm above the top edge of the humidifier
:
Initially, the steam hose is led with an
upslope of at least 20 % over a minimum height of 300
mm
above the top edge of the humidifier and then down to the steam distribution pipe with a
minimum slope of 5 %
.
– The steam hose should be kept as short as possible (
max. 4 m
) while observing the
minimum
bend radius of 300 mm
.
Important!
Allowance must be made for a
pressure loss of 10 mm
water column (approx. 100 Pa)
per meter steam hose.
Note
: If your particular installation exceeds the maximum steam hose length of 4 m contact your
Condair representative. In any case, steam hoses longer than 4 m must be insulated in their
entire length.
– Reductions in the cross section such as kinks should be avoided throughout the entire length of
the hose. The installation of a stop cock in the steam hose is not permissible.
min. 300 mm
Rmin.300 mm
min. 5 %
min. 20 %
max. 4 m
min. 300 mm
Rmin.
300 mm
min. 20 %
max. 4 m
max. 4 m
min. 5 %
Rmin. 300 mm
max. 4 m
min. 300 mm
min. 20 %
min. 300 mm
min. 20 %
min. 5 %
Rmin.
300 mm
min. 20%
Содержание EL2
Страница 1: ...Installation and Operating Instructions Electrode Humidifiers 2549892 EN 1112 Condair EL2 ...
Страница 2: ......
Страница 68: ...68 Condair EL2 23 32 32 45 Dimensions in mm ø22 492 670 69 351 180 182 246 180 180 50 547 223 163 118 233 ...
Страница 69: ...69 Notes ...
Страница 70: ...Notes ...
Страница 71: ... Condair Ltd Printed in Switzerland Technical modifications reserved ...