54
7.3.2 Disassembly and assembly of the cleanable steam cylinder type D...
1. Fasten electrode snap fastenings and push electrodes approx. 2 cm downwards into the steam
cylinder.
2. Release clamp clips of the cylinder cover and raise cover.
3. Remove carefully electrodes by lifting upwards.
4. Remove O-rings from the electrodes.
Note: Intact O-rings can be reused.
The
assembly
of the cleanable steam cylinder follows the reverse sequence.
Observe the follow ing
:
– Before assembling the steam cylinder, check the O-ring in the steam cylinder cover and the
O-rings on the electrodes for damage, and replace if necessary. Make sure to relocate O-rings
correctly.
– Insert electrodes into steam cylinder cover and push them upwards until the snap fasteners engage.
– Place the cylinder cover (with mounted O-ring) in the correct position (align the two cams on the
steam cylinder body with the corresponding grooves in the cylinder cover) on the cylinder body
and secure cover with the fastening clips.