45
6
Operation
6.1
Function of the display and operating elements
Drain/Info key
– press key
shortly
: Opens and closes the drain valve (manual
draining).
Note: the drain valve is automatically closed after 10 minutes.
– press key for a
extended period of time (>3 sec.)
: activating the
info mode
red LED “Error”
– in normal operating mode
– The LED lights in case of a malfunction of the unit. Further
operation is no longer possible
, the heating voltage is inter-
rupted.
– The LED flashes alternately with the green LED if the external
safety chain (ventilation interlock, safety humidistat, etc.) is
open.
– in info mode
LED flashes in intervals if a malfunction is present. The number of
“flashes” per interval indicates the left digit of the error code.
yellow LED “Warning and info indication”
– in normal operating mode
The LED lights if the cylinder maintenance is due (see chapter 7)
or the maintenance indication is not reset after the maintenance
(see chapter 7.6).
– in info mode
LED flashes in intervals if a malfunction is present. The number of
“flashes” per interval indicates the right digit of the error code.
green LED “Steam”
– in normal operating mode
– The LED lights if the unit produces steam.
– The LED flashes alternately with the red LED if the external
safety chain (ventilation interlock, safety humidistat, etc.) is
open.
– in info mode
LED flashes in intervals. The number of “flashes” per interval mul
-
tiplied by 10 indicates the current steam output in %.
Unit switch
Switches the unit on and off. The switch is illuminated when the unit
is switched on.
Содержание EL2
Страница 1: ...Installation and Operating Instructions Electrode Humidifiers 2549892 EN 1112 Condair EL2 ...
Страница 2: ......
Страница 68: ...68 Condair EL2 23 32 32 45 Dimensions in mm ø22 492 670 69 351 180 182 246 180 180 50 547 223 163 118 233 ...
Страница 69: ...69 Notes ...
Страница 70: ...Notes ...
Страница 71: ... Condair Ltd Printed in Switzerland Technical modifications reserved ...