General description
Description of the controller system (with all options)
InteliLite iL-MRS is a comprehensive controller for single generating sets. IL-MRS 15/16 features
extended support of electronic engines.
InteliLite controllers are equipped with a powerful graphic display showing icons, symbols and bar-
graphs for intuitive operation, which sets, together with high functionality, new standards in Gen-set
controls.
InteliLite automatically starts the Gen-set, closes the Gen-set C.B. when all conditions are met, then
stops the engine on external signal or by pressing push buttons.
InteliLite provides gas engine support without ventilation.
The key feature of InteliLite is its easy-to-use operation and installation. Predefined configurations for
typical applications are available as well as user-defined configurations for special applications.
What is in the package?
Accessories
Description
Optional / Obligatory
IL – MRS
InteliLite central unit
Obligatory
iGL -RA15
Remote announciator
Optional for MRS15/16
iG-IOM/PTM
I/O extension module
Optional for MRS15/16
AT-LINK-CONV
External RS232 interface
Optional for MRS10/11
Remote announciator iGL - RA15
The remote announciator iGL-RA15 can be connected to the MRS15/16 unit via CAN bus. Any of the
binary outputs can be configured (using LiteEdit software) to each LED diode on the RA15. The
module can be also enabled or disabled using LiteEdit software.
See the documentation of RA15 for the technical and function description.
iG IOM/PTM module
iG-IOM and iGS-PTM modules are I/O extension modules equipped with 8 binary inputs, 8 binary
outputs, 4 analogue inputs and one analogue output. The module can be used for MRS15/16 only.
Binary inputs and outputs are configurable the same way like inputs and outputs on iL.
Analogue inputs are configurable like iL with the limitation that the binary and tristate mode
can not be used on PTM module.
The protection of analogue IOM/PTM inputs is activated by overcrossing the limits, active only
when the engine is running.
iG-IOM analogue inputs are resistive (the same parameters like iL) 0
Ω
-2,4 k
Ω
. The module
IOM is designed for especially VDO resistive sensors.
iGS-PTM analogue inputs are configurable by jumpers to ranges 0-250
Ω
, 0-100mV, 0-20mA.
The module can be used especially for Pt100 sensors and current sensors. The module PTM
is not suitable for VDO temperature sensor.
See the documentation of iGS-PTM for the technical and function description.
InteliLite – MRS10/11/15/16, SW version 2.2, ©ComAp – November 2004 6
IL-MRS-2.2.pdf