ComAp InteliLite MRS10 Скачать руководство пользователя страница 42

 

JOHN DEERE 

IL-CU binary output description 

John Deere 21 pin Deutsch connector 

Start output 

Fuel output 

G (switched ECU power),J (ignition) 

 

IL-CU CAN description 

John Deere 21 pin Deutsch connector 

CAN bus common 

Screen for the J1939 cable. 

CAN bus H 

CAN bus L 

 

CUMMINS ISB/ISBE 

IL-CU binary output description 

Cummins ISB OEM Harness connector B 

Start output 

connects directly to engine starter solenoid 

Fuel output 

39 

 

IL-CU CAN description 

Cummins ISB 9 pin Deutsch connector 

CAN bus common 

SAE J1939 shield - screen for J1939 cable. 

CAN bus H 

SAE J1939 signal 

CAN bus L 

SAE J1939 return 

 

InteliLite – MRS10/11/15/16, SW version 2.2, ©ComAp – November 2004                                             42 
IL-MRS-2.2.pdf 

Содержание InteliLite MRS10

Страница 1: ...rating Gen sets IL CU MRS10 11 15 16 unit SW version 2 2 November 2004 User guide Copyright 2004 ComAp s r o Written by Adéla Klimentová Prague Czech Republic ComAp spol s r o Světova 7 180 00 Praha 8 Czech Republic Tel 420 2 66316661 Fax 420 2 66316647 E mail info comap cz www comap cz ...

Страница 2: ... list 22 Analog inputs 27 Setpoints 28 Password 28 Basic settings 28 Engine params 29 Engine protect 32 Gener protect 33 Sensor spec 36 IOM module 36 ECU controlled engine support 38 Values read from ECU 39 Diagnostic messages read from ECU 39 Analog inputs 40 J1939 connection description 41 Sensor specification 43 Default sensor settings 43 Operator interface 44 Pushbuttons and LEDs MRS10 11 15 1...

Страница 3: ...eEdit 56 Modbus protocol 56 Remote communication 62 Recommended ISDN modem 62 Recommended GSM modem 62 Mobile SIM card setting 62 Technical data 63 Power supply 63 Operating conditions 63 Low Temperature modification 63 Dimensions and weight 64 Generator 64 Binary inputs and outputs 64 Analog inputs 64 Speed pick up input 65 RS232 interface 65 CAN bus interface 65 InteliLite MRS10 11 15 16 SW vers...

Страница 4: ...Disconnect remote control via RS232 line Disconnect input REMOTE START STOP or Disconnect output STARTER and outputs GCB CLOSE OPEN Because of large variety of InteliLite parameters settings it is not possible to describe any combination Some of InteliLite functions are subject of changes depend on SW version The data in this manual only describes the product and are not warranty of performance or...

Страница 5: ...orrect software Similarly use only Chinese HW together with Chinese SW CAUTION Dangerous voltage In no case touch the terminals for voltage and current measurement Always connect grounding terminals In any case do not disconnect InteliLite CT terminals Adjust set points All parameters are preadjusted to their typical values But the set points in the Basic settings settings group must be adjusted b...

Страница 6: ...mote announciator iGL RA15 can be connected to the MRS15 16 unit via CAN bus Any of the binary outputs can be configured using LiteEdit software to each LED diode on the RA15 The module can be also enabled or disabled using LiteEdit software See the documentation of RA15 for the technical and function description iG IOM PTM module iG IOM and iGS PTM modules are I O extension modules equipped with ...

Страница 7: ...AI3 FUEL RPM IN RPM GND BINARY INPUTS GEN CURRENT 0 5 A GENERATOR VOLTAGE 3 x 230 400 V BI1 BI2 BI3 BI4 BI5 BI6 LB 16 N L 1 L 2 L 3 L3l L2l L1l COM EXTENSION MODULE iL MRS 15 Hint EXTENSION MODULE and TEST PORT serves for Extension IGS PTM or IG IOM and IGL RA15 CAN bus connection only This port is used for production tests as well InteliLite MRS10 11 15 16 SW version 2 2 ComAp November 2004 7 IL ...

Страница 8: ...ite 113 x 175 mm 4 4 x 6 9 Only for service purpose IL MRS 10 11 IL MRS 15 16 AT LINK CONV InteliLite MRS 15 iL 185 7 3 170 8 87 4 2 5 1 7 4 5 1 8 1 1 0 4 3 2 1 2 RS 232 Cable Extension module via CAN bus 1 3 0 5 1 1 2 3 4 8 1 1 3 4 4 1 InteliLite MRS10 11 15 16 SW version 2 2 ComAp November 2004 8 IL MRS 2 2 pdf ...

Страница 9: ...ENOID PRESTART ALARM READY TO LOAD D CHRG ALTERNATOR POWER 8 36 V DC RS 232 D BOOT JUMPER BO3 BO4 BO5 BO6 BO1 START BO2 FUEL BINARY OUTPUTS ANALOG INPUTS RPM COM AI1 OIL AI2 TEMP AI3 FUEL RPM IN RPM GND BINARY INPUTS GEN CURRENT 0 5 A GENERATOR VOLTAGE 3 x 230 400 V BI1 BI2 BI3 BI4 BI5 BI6 LB 16 N L 1 L 2 L 3 L3l L2l L1l COM EXTENSION MODULE iL MRS 15 ECU Hint From IL 2 1 it is possible to start V...

Страница 10: ...inst lighting strikes The maximum allowable current through the controller s negative terminal is 4A this is dependent on binary output load For the connections with 12VDC power supply the InteliLite includes internal capacitors that allow the controller to continue operation during cranking if the battery voltage dip occurs If the voltage before dip is 10V after 50ms the voltage recovers to 7 V t...

Страница 11: ...ower up 12VDC Battery iL CU HUGE LOADS STARTER T1A Binary output protections Do not connect binary outputs directly to DC relays without protection diodes even if they are not connected directly to controller outputs K1 K1 K2 K2 24VDC controller T1A Fuse Fuse Battery DC relays Grounding To ensure proper function Use as short as possible cable to the grounding point on the switchboard Use cable min...

Страница 12: ...InteliLite MRS10 11 15 16 SW version 2 2 ComAp November 2004 12 IL MRS 2 2 pdf ...

Страница 13: ...nsure proper function Use cables of 2 5mm2 Use transformers to 5A Connect CT according to following drawings L1 L2 L3 N G COM L1l K L k l L2l K L k l L3l K L k l Voltage measurement G GENERATOR MAINS L3 L2 L1 N L1 L2 L3 N L3 L2 L1 N Hint Switchboard lighting strikes protection according standard regulation is expected InteliLite MRS10 11 15 16 SW version 2 2 ComAp November 2004 13 IL MRS 2 2 pdf ...

Страница 14: ...formers to 5A Connect CT according to following drawings Terminals L2l and L3l are opened L1 N G COM L1l K L k l L2l L3l Set points adjustment To run a single phase application the following set points have to be set Gener protect Curr unbal to 200 Gener protect Curr unbal del to 60 0 s Hint In version 1 4 and lower increase Basic setting Nomin current to avoid activation of current unbalance prot...

Страница 15: ...tection direction Protection Under Fls Under step and Sensor fail activates protection Sensor characteristic Sensor Curve A Curve B Curve C PT 1000 NI 1000 VDO Temp VDO Press VDO Level 4 20mA 100 4 20mA 60 Pt100 Ni100 0 20mA 100 4 20mA 100 0 100mV 100 iL IOM PTM iL IOM PTM iL IOM PTM iL IOM iL IOM iL IOM iL IOM PTM iL IOM PTM iL IOM iL IOM PTM PTM PTM PTM PTM User curve A User curve B User curve C...

Страница 16: ...stive input Common point of IL CU analog inputs is connected to COM terminal Analog inputs are designed for resistive sensors with resistance in range of 0Ω to 2 4kΩ To ensure a proper function use shielded cables especially for length over 3m Current output transducers IL CU analog inputs are mainly designed for resistor sensors In special case transducers to 4 20mA output can be used for oil mea...

Страница 17: ...aracters Set to Bar Contact type selection of polarity only when analog input is configured as Binary or Tri state When is analog input configured as analog this setting has no sense NC polarity of binary or tri state input NO polarity of binary or tri state input Sensor selection of sensor characteristic Unused input when Analog input is not used On the InteliLite screen is displayed value no ala...

Страница 18: ... separate triplet of setpoints Wrn level Sd level Anl Inp del Names of these setpoints are fix defined Number of decimal points of Wrn level1 and Sd level is the same as the configured number of decimal points of measured value Binary inputs Binary outputs Battery iL 4k7 Ω Power Supply Battery iL LOAD Power Supply InteliLite MRS10 11 15 16 SW version 2 2 ComAp November 2004 18 IL MRS 2 2 pdf ...

Страница 19: ...l data Communication interface CAN cable shielding connect to IL CU COM terminal IL CU contains internal fix 120 ohm resistor and must be located on the CAN bus end New IG IOM and IGS PTM units contain internal jumper removable 120 ohm resistor in older IOM types are fix resistors To be sure check resistor presence by ohmmeter Unit with internal resistor connect to the end of CAN line Following co...

Страница 20: ...cters ASCII string NC Normally closed Contact type NO Normally opened Warning Alarm type Shut down All the time Alarm active Engine running only Rem start stop External request for engine run AUT mode only Emergency stop If the input is opened shut down is immediately activated Input is inverted normally closed in default configuration Hint In case of controller hardware or software fail safe stop...

Страница 21: ... same function as Stop button on the InteliLite front panel It is active in MAN mode only FaultResButton Binary input has the same function as Fault reset button on the InteliLite front panel HornResButton Binary input has the same function as Horn reset button on the InteliLite front panel GCB button Binary input has the same function as GCB button on the InteliLite front panel It is active in MA...

Страница 22: ... output opens the fuel solenoid and enables the engine start The output opens if Emergency stop comes or Cooled gen set is stopped or in pause between repeated starts Ignition The output closes after reaching value of CrankRPM fixed 30RPM Opens after stopping of the engine or in pause during repeated start Prestart The output closes prior to the engine start Prestart and opens when START RPM speed...

Страница 23: ... opens if alarm is not active and FAULT RESET is pressed Air valves Closes together with Prestart Opens after the engine is stopped Stopped engine conditions RPM 0 Engine params Starting Poil D when enabled GenParamsOK The output is copy of generator status LED on iL front panel The output is closed if genset is running and all genset electric values are in limits Alarm The output closes if any wa...

Страница 24: ...SET is pressed Hint Treshhold level for D input is 80 supply voltage Vgen failed The output closes if the generator over under voltage shutdown alarm or voltage asymmetry shutdown alarm activates The output opens if alarm is not active and FAULT RESET is pressed fgen failed Output closes if the generator over under frequency shutdown alarm activates The output opens if alarm is not active and FAUL...

Страница 25: ... reset during start procedure probably due to weak battery The output opens if alarm is not active and FAULT RESET is pressed V batt failed Output closes when battery over under voltage warning appears The output opens if alarm is not active and FAULT RESET is pressed Common Wrn Output closes when any warning alarm appears The output opens if No warning alarm is active and FAULT RESET is pressed C...

Страница 26: ...put is closed if OFF mode is selected MAN mode The output is closed if MAN mode is selected AUT mode The output is closed if AUT mode is selected FuelLevel Output closes if the Fuel level shutdown alarm activates FuelLevelWrn Output closes if the Fuel level warning alarm activates Running Output closes if the engine is in Running state ServiceTime Output closes if the ServiceTime alarm activates T...

Страница 27: ...o ECU in case of engine stop request ECU CommError The output is an inversion of binary output ECU CommOK i e the output is closed when ECU is not communicating and all values from ECU show Communication error causes stop of the engine Analog inputs Three analog inputs for resistive sensor 0 to 2400 Ω measuring Each analog input can be adjusted to convert resistor measured value to displayed value...

Страница 28: ...inal power of the generator Step 1kW Range 1 4000 kW Nominal current A It is current limit for generator IDMT over current and short current protection and means maximal continuous generator current See Generator protections 2Inom del Ishort setpoints Nominal current can be different from generator rated current value Step 1 A Range 1 5000 A CT Ratio 5A Gen set phases current transformers ratio St...

Страница 29: ...in Range 0 60 min Default value 0 means that the display lights all the time ControllerMode OFF MAN AUT Equivalent to Controller mode changes by MODE or MODE buttons Hint Controller Mode change can be separately password protected RS232 mode STANDARD MODBUS CumminsMB Communication protocol switch Standard LiteEdit communication protocol Modbus Modbus protocol CumminsMB Protocol for communication w...

Страница 30: ...emps Max number of crank attempts Step 1 Range 1 10 Idle time s Idle time delay starts when RPM exceeds Start RPM Start fail is detected when during Idle state RPM decreases below 2 During the Idle time timer running the binary output IDLE NOMINAL is opened when it elapses the IDLE NOMINAL output closes Binary output IDLE NOMINAL opens during Cooling period again Step 1 s Range 0 600 s Start RPM R...

Страница 31: ...otections are active IDLE Cooling is executed at Idle speed and generator protections are switched off Hint Binary output IDLE NOMINAL must be configured and connected to speed governor Engine Idle speed must be adjusted on speed governor Fuel solenoid DIESEL GAS Determines behavior of the Binary output FUEL SOLENOID DIESEL Output closes 1 sec before Binary output STARTER The output opens if Emerg...

Страница 32: ...del time The time starts after reaching Start RPM Step 1s Range 0 300 s Horn timeout s Max time limit of horn sounding Set to zero if you want to leave the output HORN open Step 1s Range 0 600 s Overspeed Threshold for over speed protection Step 1 of nominal RPM Range 100 150 AnlInp1 level1 Bar Warning threshold level for ANALOG INPUT 1 Step 0 1 bar Range AnlInp1 level2 10000 AnlInp1 level2 Bar Sh...

Страница 33: ... undervolt 40 V Batt volt del s Delay for low battery voltage alarm Step 1s Range 0 600 s NextServTime h Counts down when engine running If reaches zero an alarm appears Step 1h Range 0 65535h Gener protect Hint All electric protections when activated result in shutdown Overload Threshold for generator overload in of Nominal power Step 1 of Nominal power Range 0 200 Overload del s Delay for genera...

Страница 34: ...tion time is limited up to 900 sec 15 minutes IDMT protection is not active for Reaction time values longer than 15 minutes Igen is maximal value of all measured phases of generator current EXAMPLE of Reaction time for different over current levels Values in column 200 are 2Inom del Overcurrent 200 2Inom del 100 101 110 0 2 s No action 20 s 2 s 2 s No action 200 s 20 s Reaction time 20 s No action...

Страница 35: ...voltage Range 0 Gen V Gen V del s Delay for generator undervoltage and overvoltage alarm Step 0 1s Range 0 60 s Volt unbal Threshold for generator voltage unbalance alarm Step 1 of Nominal voltage Range 0 100 of Nominal voltage Volt unbal del s Delay for generator voltage unbalance alarm Step 0 1s Range 0 60 0 s Gen f Shutdown level for generator overfrequency Step 0 1 of Nominal frequency Range G...

Страница 36: ... kW 20mA Range 1 32000 kW 20mA AnlInIOM1 lev1 The level for IOM ANALOG INPUT 1 alarm detection Step 1 Range 100 10000 AnlInIOM1 lev2 The level for IOM ANALOG INPUT 1 alarm detection Step 1 Range 100 10000 AnlInIOM1 del s Delay for IOM ANALOG INPUT 1 alarm Step 1 s Range 0 180 s AnlInIOM2 lev1 The level for IOM ANALOG INPUT 2 alarm detection Step 1 Range 100 10000 AnlInIOM2 lev2 The level for IOM A...

Страница 37: ...IOM ANALOG INPUT 4 alarm detection Step 1 Range 100 10000 AnlInIOM4 del s Delay for IOM ANALOG INPUT 4 alarm Step 1 s Range 0 180 s The protection of IOM PTM inputs is activated by overcrossing the limits CalibrAInIOM 1 2 3 4 Calibrating constant to adjust the measured value of IOM PTM analog inputs Physical dimension of calibrating constant is corresponding to Analog input Step 1 Range 1000 1000 ...

Страница 38: ...cessary to set the setpoint Basic settings RS232 mode CUMMINSMB Loss of communication causes shutdown of the running engine On the contrary the ECU can be switched off at quiescent engine that means not communicating ECU is in that moment normal situation All values from ECU shall show but no alarm is displayed The output ECU CommOK follows the real situation that means it is not active anytime wh...

Страница 39: ...45 QSK60 only Diagnostic messages read from ECU Diagnostic messages are read and displayed in extra ECU Alarm list For Standard J1939 SPN Suspect Parameter Number FMI Failure Mode Identifier and OC Occurrence Counter are shown together with verbal description if available One SPN Suspect Parameter Number FMI Failure Mode Identify couple describes one fail information If FMI is equal to 0 or 1 WRN ...

Страница 40: ...Cyl3 FC C300 C306 PDEInjctorCyl4 FC C400 C406 PDEInjctorCyl5 FC C500 C506 PDEInjctorCyl6 FC C600 C606 PDEInjctorCyl7 FC C700 C706 PDEInjctorCyl8 FC E200 OverheatProt FC E600 CoordEmergStop Analog inputs Reading of mentioned values from ECU enables to use analog inputs of the unit for other purposes e g measuring displaying and alarm activation related to various quantities The configuration thus a...

Страница 41: ... 10 pin EMS B1 connector GND POWER D IL MRS15 16 BINARY BO2 OUTPUTS FUEL BO1 ECU CommOK EXTENSION L MODULE COM H Engines not started via CAN bus PERKINS 2800 series IL CU binary output description Perkins Customer interface connector Start output connects directly to engine starter solenoid Fuel output 1 10 15 33 34 powers up ECU and enables the injectors IL CU CAN description Perkins Customer int...

Страница 42: ...cable CAN bus H V CAN bus L U CUMMINS ISB ISBE IL CU binary output description Cummins ISB OEM Harness connector B Start output connects directly to engine starter solenoid Fuel output 39 IL CU CAN description Cummins ISB 9 pin Deutsch connector CAN bus common SAE J1939 shield screen for J1939 cable CAN bus H SAE J1939 signal CAN bus L SAE J1939 return InteliLite MRS10 11 15 16 SW version 2 2 ComA...

Страница 43: ...ed to all calculations e g instead of 70 C 73 C or e g instead of 5 C 6 C Note The calibration must be done at the operational point of the analog input e g 80 C 4 0Bar etc Default sensor settings Analog input 1 6 points VDO characteristic pressure measuring in bar Analog input 2 10 points VDO characteristic temperature measuring in C Analog input 3 2 points VDO fuel level sensor 0 10Ω 100 180Ω Fo...

Страница 44: ...election of the display mode MEASUREMENT ADJUSTEMENT 10 Select the set point select the screen or increase set point value 11 Select the set point select the screen or decrease set point value 12 ENTER Confirm set point value LEDs 13 14 15 GEN VOLTAGE PRESENT GREEN LED is on if gen voltage is present and within limits 16 GEN SET FAILURE RED LED starts flashing when gen set failure occurs After FAU...

Страница 45: ...o select requested set point 5 Set points marked are password protected 6 Press ENTER to edit 7 Use or to modify the set point When or is pressed for 2 sec auto repeat function is activated 8 Press ENTER to confirm or PAGE to leave without change 9 Press PAGE to leave selected set points group How to change the display contrast Press ENTER and or at the same time to adjust the best display contras...

Страница 46: ...ms is added It is displayed one screen above the standard alarm list on the controller display or under the standard alarm list in Control window of LiteEdit also since version 2 0 If an alarm appears in this alarm list it is signalized in the standard alarm list and by exclamation mark on the main measure screen Control from the front panel One screen up down Enter Cursor move within the ECU alar...

Страница 47: ...r phase Power factor total and per phase React power total and per phase Appar power total and per phase Statistic Run hours Number of starts Kilowatt hours kWh total Reactive power hours kVAh total only NextServTime ECU AlarmList Diagnostic messages are read from ECU and displayed in this second alarm list For Standard J1939 engines SPN Suspect Parameter Number FMI Failure Mode Identifier and OC ...

Страница 48: ...629 275h FLS Controller 1 EngCoolTemp WRN _____________________ SPN 110 OC 7 FMI 3 Hint For FMI 0 and 1 WRN is displayed For other FMI codes FLS is displayed Alarm list InteliLite MRS10 11 15 16 SW version 2 2 ComAp November 2004 48 IL MRS 2 2 pdf ...

Страница 49: ...NE PROT GEN BASIC GEN PROTECT MAINS FAIL ENTER PAGE Next Screen Next Screen OFF 586 500 1000 14 23 15 12345h 0 kW MAN AUTO ENTER ENTER Parameter setting 1 Set cursor by buttons 2 Press to editing mode 3 Adjust parameter by buttons 4 Press to write parameter into memory Press to cancel of editing mode PAGE InteliLite MRS10 11 15 16 SW version 2 2 ComAp November 2004 49 IL MRS 2 2 pdf ...

Страница 50: ...mplified MODE MAN Engine start stop request is given by pressing buttons START and STOP MODE AUT Engine start stop request is given by binary input REM START STOP State Condition of the transition Action Next state Start request PRESTART on Prestart time counter started Prestart RPM 2 or Oil pressure detected or Gen voltage 10V Stop Stop fail Ready OFF mode selected or Shut down alarm active Not R...

Страница 51: ...UEL SOLENOID off STOP SOLENOID on READY TO LOAD off Shutdown Cooling time elapsed FUEL SOLENOID off STOP SOLENOID on Stop RPM 0 or any other shutdown condition FUEL SOLENOID off STOP SOLENOID on Shutdown Cooling Start request READY TO LOAD on 1 Running RPM 0 Oil pressure not detected Vgen 10V Ready Stop 60 sec Elapsed Stop Stop fail 1 if all generator parameters OK and MinStab Time elapsed indicat...

Страница 52: ... outputs GCB CLOSE OPEN FUEL SOLENOID STARTER and PRESTART to stop the engine immediately Alarm outputs and common shutdown output are closed Active or not reset protection disables start Possible shut down alarms See List of possible events Alarm time chart All the time configured protections I I RPM mains failure detection GCB opened Engine running only protections engine water temperature luboi...

Страница 53: ...can be detected GEN L1 neg generator phase L1 is inverted GEN L2 neg generator phase L2 is inverted GEN L3 neg generator phase L3 is inverted Wrong phase sequence and inverted polarity It is combination of both previous alarms G ph L1 neg wrong generator phase sequence and phase L1 is inverted G ph L2 neg wrong generator phase sequence and phase L2 is inverted G ph L3 neg wrong generator phase seq...

Страница 54: ...oint Water Temp Wrn WRN YES Water temperature is greater than Wrn Water temp setpoint Water Temp Sd SD NO Water temperature is greater than Sd Water temp setpoint Fuel Level Wrn WRN YES Fuel level is smaller than Wrn Fuel Level setpoint Fuel Level Sd SD NO Fuel level is smaller than Sd Fuel Level setpoint Analog inp IOM PTM Wrn WRN YES Warning alarm configurable on the input of IG IOM IGS PTM Anal...

Страница 55: ...the engine when the RPM reache the value of Start RPM setpoint the starter is switched off and the speed of the engine can drop under Start RPM again Than the Underspeed protection comes active EmergencyStop SD NO If the input Emergency stop is opened shutdown is immediately activated PickupFault SD NO Failure of magnetic pick up sensor for speed measurement Stop fail SD YES Gen set stop failed Wr...

Страница 56: ...0 VDC CONTROLLER Battery Required the same voltage potential between GND s RS 232 PC software LiteEdit On the PC for direct or modem connection has to be installed the ComAp s software package LiteEdit based on Windows 95 or newer platform LiteEdit enables read the quantities adjust all set points control the engine configure the controller select software configuration modify alarm inputs and out...

Страница 57: ...unication object list exported from default archive Setpoints MRS10 11 15 16 Name Firmware ver Application Date App ver Ser num Filename InteliLite IL 2 1 R 10 11 2004 MRS16 30 11 2004 2 1 0200FFFF MRS16 2 1 ail Group Name Value Dimension Password Com obj Low limit High limit Data type Basic settings Gen set name InteliLite No 8637 Short string Basic settings Nomin power 200 kW No 8276 1 4000 Unsi...

Страница 58: ... Integer 16 Engine protect AnlInp1 level2 1 0 Bar No 8370 10 0 2 0 Integer 16 Engine protect AnlInp1 del 3 s No 8365 0 180 Unsigned 16 Engine protect AnlInp2 level1 80 C No 8375 100 90 Integer 16 Engine protect AnlInp2 level2 90 C No 8376 80 10000 Integer 16 Engine protect AnlInp2 del 5 s No 8371 0 180 Unsigned 16 Engine protect AnlInp3 level1 20 No 8381 10 10000 Integer 16 Engine protect AnlInp3 ...

Страница 59: ...No 8766 100 10000 Integer 16 IOM PTM module AnlInIOM1 del 0 s No 8770 0 180 Unsigned 16 IOM PTM module AnlInIOM2 lev1 0 U5 No 8763 100 10000 Integer 16 IOM PTM module AnlInIOM2 lev2 0 U5 No 8767 100 10000 Integer 16 IOM PTM module AnlInIOM2 del 0 s No 8771 0 180 Unsigned 16 IOM PTM module AnlInIOM3 lev1 0 U6 No 8764 100 10000 Integer 16 IOM PTM module AnlInIOM3 lev2 0 U6 No 8768 100 10000 Integer ...

Страница 60: ... 8565 Integer 16 Generator Appar pwr L1 0 kVA 8530 Integer 16 Generator Appar pwr L2 0 kVA 8531 Integer 16 Generator Appar pwr L3 0 kVA 8532 Integer 16 Generator Pwr factor 0 00 8204 Integer 8 Generator Pwr factor L1 0 00 8533 Integer 8 Generator Pwr factor L2 0 00 8534 Integer 8 Generator Pwr factor L3 0 00 8535 Integer 8 Generator Load char 8395 Char Generator Load char 1 8626 Char Generator Loa...

Страница 61: ...ecode 2481875985 9090 Unsigned 32 RA15 module BOutRA15 000000000000000 9849 Binary 16 IOM PTM module AnInIOM 1 0 U4 8978 Integer 16 IOM PTM module AnInIOM 2 0 U5 8759 Integer 16 IOM PTM module AnInIOM 3 0 U6 8760 Integer 16 IOM PTM module AnInIOM 4 0 U7 8761 Integer 16 IOM PTM module BInpIOM 00000000 8602 Binary 16 IOM PTM module BOutIOM 00000000 8604 Binary 16 ECU Fuel rate L h 9860 Unsigned 16 E...

Страница 62: ...independent on LiteEdit Start MS Windows Start Program files LiteEdit Gm_setup exe Select COM port Select iG CU IS CU or iG MU unit Press Setup button Follow commands in GSM Modem Setup window Typical baud rate for GSM data communication is 80 to 90 Bps Hint It is strongly recommended to use the same type of modem on the both sides IL and PC of connection Analog modem GSM modem or GSM modem Analog...

Страница 63: ...rature modification LCD display limits controller operating temperature range to 20 o C 70 o C even if the other electronic components work in wider temperature range Internal preheating foil is mounted in InteliLite LT to extend display operational temperature range Preheating starts at temperature below 5 o C and preheating power depends on temperature and power supply voltage Technical data IL ...

Страница 64: ...al Voltage measurement tolerance 2 from the Nominal voltage Overvoltage class III EN61010 Binary inputs and outputs Binary inputs Number of inputs 6 Input resistance 4 7 kΩ Input range 0 36 VDC Switching voltage level for close contact indication 0 2 V Max voltage level for open contact indication 8 36 V Contact relay outputs Number of outputs 2 Electric life cycle min 100 000 switching cycles Max...

Страница 65: ...y separated Maximal CAN bus length 200m Speed 250kBd Nominal impedance 120Ω Cable type twisted pair shielded Following dynamic cable parameters are important especially for maximal 200 meters CAN bus length and 32 iS COM units connected Nominal Velocity of Propagation min 75 max 4 4 ns m Wire crosscut min 0 25 mm2 Maximal attenuation at 1 MHz 2 dB 100m Recommended Industrial Automation Process Con...

Отзывы: