Events specification
Protection
type
Information on binary
output available (See list
of
Binary outputs
)
Description
typically after downloading
new firmware or changing of
the parameter. The controller
stays in INIT mode. Check all
parameters, write at least one
new parameter.
Vgen <, >
SD
YES
The generator voltage is out of
limits given by
Gen <V
and
Gen >V
setpoints.
Vgen unbl
SD
NO
The generator voltage is
unbalanced more than the
value of
Volt unbal
setpoint.
Fgen <,>
SD
YES
The generator frequency is out
of limits given by
Gen >f
and
Gen <f
setpoints.
Igen unbl
SD
NO
The generator current is
unbalanced.
Overload
SD
YES
The load is greater than the
value given by
Overload
setpoint.
Overspeed
SD
YES
The protection comes active if
the speed is greater than
Overspeed
setpoint.
Underspeed
SD
YES
During starting of the engine
when the RPM reache the
value of
Start RPM
setpoint
the starter is switched off and
the speed of the engine can
drop under
Start RPM
again.
Than the Underspeed
protection comes active.
EmergencyStop
SD
NO
If the input
Emergency stop
is
opened shutdown is
immediately activated.
PickupFault
SD
NO
Failure of magnetic pick-up
sensor for speed
measurement.
Stop fail
SD
YES
Gen-set stop failed.
WrnServiceTime
WRN
NO
The period for servicing is set
by the
NextServTime
setpoint.
The protection comes active if
the running hours of the
engine reach this value.
ChrgAlternFail
WRN
YES
Failure of alternator for
charging the battery.
SprinklActive
WRN
NO
The protection is active if the
output
Sprinkler
is closed.
*Wrn RA15 fail
WRN
NO
Warning alarm in case of lost
connection to IGL-RA15
module.
*Sd IOM fail
SD
NO
Shutdown alarm in case of lost
connection to IG-IOM/IGS-
PTM module.
Wrn ECU Alarm
WRN
NO
ECU alarm list
is not empty